Hitachi RPI-0.8FSG1 Service Manual page 31

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

(1.1.7 Abnormalities of Devices)
Phenomenon
Excessively
High
Discharge
Pressure
Insufficient
Heating
Operation
Malfunction of Check Valve
of Outdoor Unit
Excessively
High Suction
Pressure
*1): Refer to TCII, SP2-K03 and SP2-L01.
Cause
Insufficient
Air Flow to
Indoor Unit
Heat
Exchanger
Excessively
High Air
Temp. to
Indoor Unit
Heat
Exchanger
Excessively
Charged
Refrigerant
Non-
Condensate
Gas in Ref.
Cycle
Clogging of
Discharge
Pr. Piping
Malfunction or Internal
Leakage of 4-Way Valve
Failure of
Bypass
Solenoid
Valve
Malfunction
or Internal
Leakage of
4-Way Valve
Discharge Temp. of
Indoor Unit is Unstable.
Check Item
Check for filter clogging.
Check for any obstacles
at inlet or outlet of
indoor unit.
Check indoor fan speed.
Check whether or not
short-circuited air exists.
Check expansion valve
opening.
Check refrigerant
quantity. *1)
Check for clogging.
Check temp. difference
between inlet and outlet
of 4-way valve.
Check temp. difference
between inlet and outlet
of check valve.
Check for leakage of
solenoid valve.
Check temp. difference
between inlet and outlet
of 4-way valve.
Check for expansion
valve of indoor unit in
the same system.
TROUBLESHOOTING
Action
(Turn OFF Main Switch)
Remove clogging.
Remove obstacles.
Replace fan motor.
Remove cause of
short-circuited air.
Correctly charge
refrigerant.
Recharge refrigerant
after vacuum pumping.
Remove clogging.
Replace 4-way valve.
Replace check valve.
Replace solenoid valve.
Replace 4-way valve.
Replace failed
expansion valve of
indoor unit.
1-21