Hitachi RPI-0.8FSG1 Service Manual page 131

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

Name of Parts
Drain-up Motor
for RCI-1.0FSG2, 1.5FSG2, 2.0FSG2,
2.5FSG2, 3.0FSG2, 4.0FSG2, 5.0FSG2
Drain-up Motor
for RCD-1.0FSG1, 1.5FSG1, 2.0FSG1,
2.5FSG1, 3.0FSG1, 4.0FSG1, 5.0FSG1
Drain-up Motor
for RPI-0.8FSG1, 1.0FSG1, 1.5FSG1
Solenoid Valve for Gas Bypass
for RAS-5FSG, 8FSG, 10FSG, 8FXG, 10FXG
RAS-5FS3, 8FS3, 10FS3, 8FX3, 10FX3
Solenoid Valve for Gas Bypass
for RAS-16FSG, 20FSG, 16FS3, 20FS3
4-Way Valve
for RAS-5FSG, 8FSG, 10FSG, 8FXG, 10FXG
RAS-5FS3, 8FS3, 10FS3, 8FX3, 10FX3
4-Way Valve
for RAS-16FSG, 20FSG, 16FS3, 20FS3
Compressor Motor
for RAS-5FS3
Compressor Motor
for RAS-8FS3, 10FS3, 16FS3, 20FS3
8FX3, 10FX3
Compressor Motor
for RAS-8FS3, 8FX3
Compressor Motor
for RAS-10FS3, 10FX3
Compressor Motor
for RAS-16FS3, 20FS3
Model
ADP-1403
KJV-1004
PJD-05230HS
ST10PA
ST10PA
RAS-5FSG
RAS-5FS3
CHV-01AJ503C1
RAS-8FSG, 8FXG
RAS-8FS3, 8FX3
RAS-10FSG, 10FXG
CHV-01AJ503H1
RAS-10FS3, 10FX3
CHV-0717
+
CHV-01AJ503H1
401DHV
401DHVM
400DHM
500DHM
600DHM
TROUBLESHOOTING
Resistance
(Ω)
256
at 20
347
at 20
447
at 20
2,018/1,245
at 20
(50/60Hz)
2,018/1,245
at 20
(50/60Hz)
CHV-0407
1,435
+
at 20
CHV-0717
1,435
+
at 20
1,435
at 20
*1.436/1.436/0.395
at 20
*1.436/1.436/0.395
at 20
*3.29/2.68/0.74
at 20
*2.73/2.22/0.572
at 20
*2.28/1.68/0.507
at 20
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
1-121