Hitachi RPI-0.8FSG1 Service Manual page 165

Inverter-driven multi-split system heat pump air conditioners
Table of Contents

Advertisement

B. Removing High Pressure Sensor and Low Pressure Sensor
(1) Remove the water-proof caps.
NOTE:
The water-proof caps are used after replacing pressure sensors.
(2) Remove the pipe of the high pressure sensor or low pressure sensor using two spanners. Firstly,
remove the check joint at the main pipe side as shown figure in 2.1.9.
(3) Remove the connector for the pressure sensors.
(4) Remove the high pressure sensor or low pressure sensor after removing each two (2) fixing screws
for the pressure sensors.
NOTE:
Put the water-proof caps on the pressure
sensors again after replacing pressure sensors.
Position of
Pressure Sensors
8 and 10HP
Only
RAS-5FSG, 5FS3
8FSG, 8FS3
10FSG, 10FS3
RAS-8FXG, 8FX3
10FXG, 10FX3
RAS-24FSG1, 24FS5
30FSG1, 30FS5
TURN OFF all power source switches.
RAS-16FSG, 16FS3
20FSG, 20FS3
Electrical Box
Low Pressure Sensor
Position of
Pressure Sensors
Adjustable Wrench or Spanner,
Tool
Phillips Screwdriver
Position of
Pressure Sensors
20HP Only
Water-proof
Cap
Screw
Screw
Firstly remove the check joint
at the main pipe.
If the sensor side is removed,
refrigerant will be discharged.
SERVICING
(2.1 Outdoor Unit)
High Pressure Sensor
Mounting Plate for
Pressure Sensors
Two Spanners
2-25