3.7.6 Connecting Earth Cable

There is an earth hole with an earth label on the bottom of the rear door of the cabinet, as shown in Figure 3-30.
When earthing, use a M6 screw to fix one end of the earth cable on the earth hole, and lead the other end through
the rubber protective ring on the bottom plate to the earth copper bar of the computer room.
Note
1. To ensure safety, the cabinet and the AC components must be reliably grounded.
2. Use a yellow-green earth cable of no less than 6mm
When fixing the M6 screw on the earth hole of the cabinet, a wrench is recommended.
3. If there is no earth block in the building where the SmartCabinet is placed, you can use a yellow-green earth cable of no less
2
than 6mm
to connect the earth terminal of cabinet with that of PMU total input, to ensure reliable earthing of the cabinet.

3.8 Configure Communication Address And Port

1. Set the addresses of the temperature sensor through the DIP switch, as shown in Figure 3-31 and Table 3-8.
Device
Front door side S01T
Rear door side S01T
2. Set the 4DI sensor address through DIP switch, as shown in Figure 3-32 and Table 3-9.
Earth hole
Screw
A amplified
Figure 3-30 Connecting earth cable
0 1 1 1 0 1
Note: 1. DIP switch in the ON position means 1,
1 2 3 4 5 6
DIP
ON
Group Num
Figure 3-31 Set the address of the temperature sensor through DIP switch
Table 3-8 DIP list for setting the temperature sensor address
DIP1 ~ DIP4
0 0 0 2
0 0 0 2
SmartCabinet Integrated Solution User Manual
Cabinet
A
2
and connect it to the earth copper bar of the computer room reliably.
or it means 0;
2. The sensor address cannot be set as 00,
which is the broadcast address.
Group
1
1
Chapter 3 Installation
DIP5 ~ DIP6
Number
0 1
1 0
31
1
2