Configure doors

11.1 Door relay time settings

Building Technologies
Fire Safety & Security Products
The next step is to configure information about doors. Depending on what the door
centrals/readers are used for, different parameters can appear in the menus.
If you have a door monitor contact installed there will be three parameters to
defined:
Unlock time = Maximum time for active relay (no buzzer).
Opening time = Maximum time for door open (no buzzer).
Door Held Warning Time = Maximum time (with buzzer) before Alert.
The reason for having separate unlock and opening times is that it is now possible
to have a shorter, fixed time when the relay is active and another, longer time to
have the door open (with a "delayed" door held warning signal).
Note that earlier versions of SiPass Entro had only a maximum opening time (= the
lock relay to be active).
The relations between these times (in worst case) can be seen in the diagram
below.
2.
1.
Door monitoring time diagram (worst case when door is held open)
1.
Unlock Time (max). Lock Relay
2.
Door opened by user. Monitored by door contact.
3.
Opening Time (max). Monitored by door contact.
4.
Door Held Warning Time (max). Warning relay (only DC22)
5.
Alert relay (only DC22)
3.
4.
052_SiPass_Entro_6_5_A24205-A335-B318_e_en
Configure doors
5.
25
10.03.2010