▪ date,
▪ time,
▪ system layout.
By confirming the system layout, you can proceed with the
installation and commissioning of the system.
1 At power ON, the quick wizard starts as long as the system
layout was NOT confirmed yet, by setting the language.
Language
Select the desired language
Confirm
Adjust
2 Set the current date and time.
Date
What date is it today?
Sun
1
Jan
2012
Confirm
Adjust
Scroll
Time
What is the current time?
00
: 00
Confirm
Adjust
Scroll
3 Set the system layout settings: Standard, Options, Capacities.
For more details, see "8.2 Basic configuration" on page 43.
A
System layout
Standard
Options
Capacities
Confirm layout
Select
Scroll
4 Confirm by pressing
.
Confirm layout
Please confirm the system
layout. The system will
restart and will be ready for
first startup.
OK
Cancel
Confirm
Adjust
5 The user interface re-initialises and you can proceed the
installation by setting the other applicable settings and
commissioning of the system.
When the installer settings are changed, the system will request to
confirm. When confirmation is complete, the screen will shortly turn
OFF and "busy" will be displayed for several seconds.
8.2

Basic configuration

8.2.1

Quick wizard: Language / time and date

#
Code
[A.1]
N/A
Language
[1]
N/A
Time and date
ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA
Daikin Altherma - Low Temperature Split
4P313775-1C – 2012.11
1
Description
8.2.2

Quick wizard: Standard

Backup heater configuration (only for *9W model)
The backup heater in a *9W model is adapted to be connected to
most common European electricity grids. Besides hardware
configuration, the backup heater type must be set on the user
interface.
#
Code
[A.2.1.5]
[5-0D]
BUH type:
▪ 1 (1P,(1/1+2)): 6 kW 1~ 230 V (*9W)
▪ 3 (3P,(1/1+2)): 6 kW 3~ 230 V (*9W)
▪ 4 (3PN,(1/2)): 6 kW 3N~ 400 V (*9W)
▪ 5 (3PN,(1/1+2)): 9 kW 3N~ 400 V
(*9W)
Space heating/cooling settings
The system can heat up or cool down a space. Depending on the
type of application, the space heating/cooling settings must be made
accordingly.
#
Code
[A.2.1.7]
[C-07]
Unit control method:
▪ 0 (LWT control): Unit operation is
decided based on the leaving water
temperature regardless the actual
room temperature and/or heating or
cooling demand of the room.
▪ 1 (Ext RT control): Unit operation is
decided by the external thermostat or
equivalent (e.g. heat pump convector).
▪ 2 (RT control): Unit operation is
decided
temperature of the user interface.
[A.2.1.B]
N/A
Only if there are 2 user interfaces (1
installed in the room, 1 installed at the
indoor unit):
▪ a: At unit
▪ b: In room as room thermostat
User interface location:
▪ At unit: the other user interface is
automatically set to In room and if RT
control is selected act as room
thermostat.
▪ In room (default): the other user
interface is automatically set to At unit
and if RT control is selected to act as
room thermostat.
8 Configuration
Description
Description
based
on
the
ambient
a
b
Installer reference guide
43