To Open/Close The Stop Valve; To Handle The Stem Cap; To Handle The Service Cap; To Connect The Refrigerant Piping To The Outdoor Unit - Daikin ERLQ004~008CAV3 Reference Manual

Altherma - low temperature split
Table of Contents

Advertisement

b Valve stem
c Field piping connection
d Stem cap
▪ Keep both stop valves open during operation.
▪ Do NOT apply excessive force to the valve stem. Doing so may
break the valve body.
▪ Always make sure to secure the stop valve with a spanner, then
loosen or tighten the flare nut with a torque wrench. Do NOT place
the spanner on the stem cap, as this could cause a refrigerant
leak.
a Spanner
b Torque wrench
▪ When it is expected that the operating pressure will be low (e.g.
when cooling will be performed while the outside air temperature
is low), sufficiently seal the flare nut in the stop valve on the gas
line with silicon sealant to prevent freezing.
Silicon sealant, make sure there is no gap.
7.4.5

To open/close the stop valve

1 Remove the valve cover
2 Insert a hexagon wrench (liquid side: 4 mm, gas side: 6 mm)
into the valve stem and turn the valve stem:
Counterclockwise to open.
Clockwise to close.
3 When the valve stem cannot be turned any further, stop turning.
The valve is now opened/closed.
7.4.6

To handle the stem cap

Take the following guidelines into account:
▪ The stem cap is sealed where indicated with the arrow. Do NOT
damage it.
▪ After handling the stop valve, make sure to tighten the stem cap
securely.
▪ For the tightening torque, refer to the following table.
▪ Check for refrigerant leaks after tightening the stem cap.
Item
Stem cap, liquid side
Stem cap, gas side
Service port cap
ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA
Daikin Altherma - Low Temperature Split
4P313775-1C – 2012.11
a
b
Tightening torque (N∙m)
13.5~16.5
22.5~27.5
11.5~13.9
7.4.7

To handle the service cap

Take the following guidelines into account:
▪ Always use a charge hose equipped with a valve depressor pin,
since the service port is a Schrader type valve.
▪ After handling the service port, tighten the service port cap
securely. For the tightening torque, refer to the table in chapter
"7.4.6 To handle the stem cap" on page 31.
▪ Check for refrigerant leaks after tightening the service port cap.
7.4.8
To connect the refrigerant piping to the
outdoor unit
1 Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.
a
b
c
a Liquid stop valve
b Gas stop valve
c Service port
2 Connect the gas refrigerant connection from the indoor unit to
the refrigerant stop valve of the outdoor unit.
7.4.9
To connect the refrigerant piping to the
indoor unit
1 Connect the liquid stop valve from the outdoor unit to the
refrigerant liquid connection of the indoor unit.
a b
a Refrigerant liquid connection
b Refrigerant gas connection
2 Connect the gas stop valve from the outdoor unit to the
refrigerant gas connection of the indoor unit.
NOTICE
It is recommended that the refrigerant piping between
indoor and outdoor unit is installed in a ducting or the
refrigerant piping is wrapped with finishing tape.
7.4.10

About checking the refrigerant piping

Checking the refrigerant piping typically consists of:
1 Checking for leaks.
7 Installation
Installer reference guide
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ehvh/x04+08s18caEhvh/x08s26ca

Table of Contents