To pump down ................74 13.2 To start and stop forced cooling ..........74 Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer. 14 Glossary ............. 75 15 Technical data ........... 76 15.1 Dimensions and service space ..........
Make sure installation, testing and applied materials ignitable dust. comply with applicable legislation (on top of the instructions described in the Daikin documentation). ▪ In places where corrosive gas (example: sulphurous acid gas) is produced. Corrosion of copper pipes or soldered parts may cause CAUTION the refrigerant to leak.
▪ When installing the earth leakage protector, make sure it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector. ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Identification NOTICE When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
The user interface is delivered as an accessory with the unit. An additional user interface is optionally available. ▪ X=Heating/cooling The additional user interface can be connected: ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
The purpose of the application guidelines is to give a glance of the ▪ For more information about the configuration settings to possibilities of the Daikin heat pump system. optimize heat pump operation, see "8 Configuration" on page 41.
▪ For your daily needs, you can use preset values and schedules. ▪ How many rooms are heated (or cooled) by the Daikin heat pump ▪ To deviate from your daily needs, you can temporarily overrule system? the preset values and schedules, use the holiday mode…...
Page 10
5 Application guidelines Benefits Combination: Under floor heating + Heat pump convectors ▪ Wireless. The Daikin external room thermostat is available in a wireless version. ▪ Space heating is provided by: ▪ Efficiency. Although the external room thermostat only sends ▪...
▪ Code: [7-02] Benefits ▪ Cost effective. ▪ Easy. Same installation as for one room, but with thermostatic valves. A Main leaving water temperature zone ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
(X2M/1 and X2M/4). The indoor unit will only supply leaving water temperature when there is an actual demand. INFORMATION To increase comfort and performance, Daikin recommends INFORMATION to install the valve kit option EKVKHPC on each heat pump To increase comfort and performance, Daikin recommends convector.
▪ Bivalent operation is only possible for space heating, NOT for domestic hot water production. Domestic hot water is always produced by the DHW tank connected to the indoor unit. ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split...
Page 14
▪ Make sure the auxiliary boiler and its integration in the system complies with applicable legislation. Setup ▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system. ▪ Integrate the auxiliary boiler as follows: Only for EHBH/X ▪...
FHL1...3 Under floor heating 55°C (50°C if outdoor temperature is low). The electrical UI User interface resistance integrated in the heat pump can higher this ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
▪ If energy prices are the same during the day and the night, ▪ Solar panels Daikin recommends to heat up the DHW tank during the day. ▪ For more information about: ▪ If energy prices are lower during the night, Daikin recommends to heat up the DHW tank during the night.
When measuring the electrical power consumption, make ▪ Per month sure ALL power input of the system is covered by the electrical power meters. ▪ Per year ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Booster heater (L ▪ 230 V and 400 V three-phase grids are combined (very uncommon), because of technical limitations of power meters. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
▪ Permanently Power limitation is also useful in combination with an energy ▪ By digital inputs management system. INFORMATION The power or current of the entire Daikin system is limited Power consumption control CANNOT used dynamically by digital inputs (maximum four steps). Each power applications with booster heater.
▪ That is NOT affected by outside air or air draught because of, for example, door opening/closing INFORMATION ▪ If this is NOT possible, Daikin recommends to connect a remote In case more than 1 digital input is closed (at the same indoor sensor (option KRCS01-1).
▪ in coastal areas or other places where the air contains high levels of salt. Corrosion may occur, ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split...
▪ Provide drain taps at all low points of the system in order to allow 15.9 mm (5/8") 16~20 mm 13 mm complete drainage of the water circuit. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
▪ In accordance with the applicable legislation, it may be necessary f Shut-off valve to install thermostatic mixing valves. g Collector (field supply) ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Changing the pre-pressure of the expansion vessel should be done by releasing or increasing nitrogen pressure through the schräder valve of the expansion vessel. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
3+GND The following illustration is an example and may NOT Power supply and match your system layout. interconnection cable to indoor unit ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
3+GND + 1 bridge 3x 400 V 4+GND Installation Opening the units 7.1.1 To open the outdoor unit 1 Remove 1 screw from the service cover. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
The maximum height of the upper protruding part of the bolts is 15 mm. (mm) a Maximum snowfall height b EKFT008CA option kit (mm) ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
The drain pan kit consists of: a Air outlet NOTICE The pedestal MUST be aligned with the backside of the U‑beam. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
▪ Use caution when passing copper tubes through walls. ▪ Protect the piping as described in the following table to prevent dirt, liquid or dust from entering the piping. ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split...
2 Remove burrs with the cut surface lacing downward so that the chips does not enter the pipe. a Service port and service port cap a Cut exactly at right angles. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Stem cap, liquid side 13.5~16.5 Checking the refrigerant piping typically consists of: Stem cap, gas side 22.5~27.5 1 Checking for leaks. Service port cap 11.5~13.9 ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
▪ Check whether the refrigerant cylinder is equipped with a siphon tube (the marking "liquid filling siphon attached" should be g Service port present). h Valve lids i Gas stop valve Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Orientation of the integrated drain and fill valves is important for servicing. 1 Install the shut-off valves on the water pipes. a Pressure relief blow-out ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
RH 80%, the thickness of the sealing materials should be at least 20 mm to prevent condensation on the surface of the sealing. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
26 and "7.1.3 To open the switch box cover of the indoor unit" on page 27. 2 Wiring should enter the unit from the top: ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split...
▪ Space cool/heat operation control 7.6.4 To connect the main power supply CAUTION Do NOT push or place redundant cable length in the unit. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Wiring is different for a NC (normal closed) valve and a NO (normal open) valve. From the left 2 Fix the cable with cable ties to the cable tie mountings. ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
2 Fix the cable with cable ties to the cable tie mountings. a Installation of EKRP1AHTA is required. 2 Fix the cable with cable ties to the cable tie mountings. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
3 Reinstall the front panel. NOTICE When closing the indoor unit cover, make sure that the tightening torque does NOT exceed 4.1 N•m. ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
ON After first power ON of the system, you are guided on the user interface to do initial settings: ▪ language, Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
RT control is selected to act as room thermostat. 8.2.1 Quick wizard: Language / time and date Code Description [A.1] Language Time and date ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 44
▪ 2 (Request): Pump operation based on request. Example: Using a room thermostat creates thermo ON/OFF condition. When there is no such demand, the pump is OFF. Remark: Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
(X2M/1 and 2). Select this value in case of connection with the wired (EKRTWA) or wireless (EKRTR1) room thermostat. ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 46
–besides by the heat pump- also be heated by thermal solar panels. Set this value if thermal solar panels installed. "5 Application guidelines" on page 8. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
5°C. See the user reference guide and/or operation manual for more details about this function. ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 48
Note: This value should be lower than [1-02] as for high outdoor than [1-08] as for high outdoor temperatures less warm water is temperatures colder water required. required. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 49
25°C~depending on outdoor unit (default: 35°C). Note: This value should be lower than [0-01] as for high outdoor temperatures less warm water is required. ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Range: 3~10°C (in steps and how the unit acts upon it. of 1°C; default value: 5°C). Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
The absolute desired tank temperature for 1 person. 30~80°C (default: 42°C) Code Description [6.3.2] Number that users can call in case of problems. ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
37~depending on outdoor unit (default: 55°C) range can be configured. [A.3.1.2.2.1] [9-05] Minimum temp (heating) 15~37°C (default: 25°C) [A.3.1.2.2.4] [9-08] Maximum temp (cooling) 18~22°C (default: 22°C) Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 53
Only applicable in case of room thermostat control. The hysteresis selection of the heat emitters) between the desired leaving water band around the desired room temperature is settable. Daikin temperature and the desired room temperature. advises NOT to change the room temperature hysteresis as it is set for an optimal use of the system.
Page 54
Note that the there is demand. See "5 Application guidelines" on page 8. outdoor temperature will be time-averaged (see "8 Configuration" on page 41). Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
+ reheat. interface. You can define preset tank temperatures: ▪ storage economic ▪ storage comfort ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 56
[7-01] Hysteresis. Temperature difference between booster heater ON and booster heater OFF temperature. The minimum hysteresis temperature is 2°C. Range: 2~40°C (default: 2) Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 57
OFF temperature. ▪ When system layout ≠ Room thermostat control: This preset value is always taken into account. Range: 5~95 minutes (default: 30) ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
5°C below the disinfection target determine — based on the outdoor temperature — which heating temperature within the duration time. source can/will provide the space heating, either the Daikin indoor unit or an auxiliary boiler. 8.3.3 Heat source settings The field setting "bivalent operation"...
See illustration below for the schematic location of ▪ 0: Solar kit this contact. For complete upwiring, see "15.6 Wiring diagram" on page 85. ▪ 1: Heat pump Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 61
When power returns after a power supply failure, the auto restart function reapplies the remote controller settings at the time of the Only for EHVH/X: Do NOT use 1 or 3. power failure. Therefore, Daikin recommends to always enable the [d-00] Backup heater Compressor function.
Page 62
▪ 1: Enabled Power consumption control Only applicable EHBH/X04+08 EHVH/X04+08. "5 Application guidelines" on page 8 for detailed information about this functionality. Pwr consumpt. control Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 63
[1-0A] Outdoor average timer: <4°C (pump will be activated for 10 minutes and disactivated after ▪ No averaging (default) 10 minutes). Daikin shall NOT be held liable for any damage resulting this functionality. ▪ 12 hours ▪ 24 hours Code Description ▪...
[A.7] Commissioning kW value Test run Amp. limits for DI kW limits for DI UFH screed dryout Air purge Priority Actuator test run ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Installer settings > Commissioning > Air purge > Circuit. There is NO water leak inside the indoor unit. 8 Select the desired circuit and press Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
(heating/cooling mode) and tank temperature (domestic hot water mode). For monitoring the temperature, go to [A.6] and select the information you want to check. ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
When using means for descaling or chemical disinfection, hot! it must be ensured that the water quality remains compliant with EU directive 98/83 EC. Checkpoints are: ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Drain hose INFORMATION To drain the tank, all the hot water tapping points need to be opened to allow air to enter the system. Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
36. The preferential kWh rate signal Wait for the power to return (2 was sent by the electricity hours max.). company ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment not made by Daikin that can be combined with product according instructions accompanying documentation.
15 Technical data 15.2 Center of gravity 15.2.1 Center of gravity: Outdoor unit UNIT 4TW60819-1 ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
The protector activates when the temperature of the backup heater becomes too high. t Drain collector (EHVX models only) u Drain gutter (EHVX models only) Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Cable tie mountings k Digital I/O PCB A4P (only for installations with solar kit or digital I/O PCB kit) l Demand PCB for power limitation ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Filter m Heat exchanger (indoor unit) n Heat exchanger (domestic hot water tank) o Domestic hot water tank p Domestic hot water in Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
(*) : standard for *HV*, optional for *HB* On/OFF thermostat (wireless) # : field supply Ext. thermistor Heat pump convector 4D077028 page 1 Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 89
EKBPHT* only if no EKBPHT* Options: bottom plate heater OR On/OFF output Only for digital I/O PCB option 4D077028 page 3 ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 90
Relay on PCB (*) = Standard for EHVH/X, optional for EHBH/X Main supply pump # = Field supply Domestic hot water pump Black Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
In case user interface is relocated 2x0.75 X5M: 1-2 A2P: P1-P2 user interface communication OPTIONAL PART Only for *KRCAL* 2 core 2x0.75 communication A2P: P1-P2 user interface 4D078494 Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 93
Regular kWh rate power supply Electrical 3~ balanced meter type 3~ unbalanced Benefit kWh rate power supply Electrical 3~ balanced meter type 3~ unbalanced 4D078288 ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 95
(2) The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to sound spectrum drawing for more information. 3TW60811-1 B page 2 ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split...
Page 96
(1) : European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current max. running current >16A and ≤75A per phase. (2) : See figure A 3TW60811-1 B page 3 Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
(12) Refer to operation range detail for diferences between *RHQ* and *RLQ* models 3D077571_B page 1 (13) DB/WB 7°C/6°C - LWC 45°C (DT = 5°C) ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
Page 98
(**) : European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase. 3D077571_B page 2 (***) : System impedance Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
In case such conditions ara expected, the *RLQ must be installed instead. These models contain countermeasures (insulation, heater sheet, ...) to prevent freeze up. 3TW60813-1A ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
1. Refer to psychometric chart for more information. 2. If condensation is expected, installation of EKHBDPCA2 - drainpan kit must be considered. 4D078990 ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
- The capacity and power input is valid for V3-models at 230V. - The capacity and power input is at maximum operation 3TW60812-1A Installer reference guide ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...
See also minimum and maximum allowed waterflow range in the technical specifications. 2) Water quality must be according to EN directive EC 98/83 EC. 4D078786 ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA Installer reference guide Daikin Altherma - Low Temperature Split 4P313775-1C – 2012.11...