To open the switch box cover of the
indoor unit
4x
7.2

Mounting the outdoor unit

7.2.1

To prepare the installation structure

Check the strength and level of the installation ground so that the
unit will not cause any operating vibration or noise.
Fix the unit securely by means of the foundation bolts in accordance
with the foundation drawing.
If the unit is installed directly on the floor, prepare 4 sets of M8 or
M10 anchor bolts, nuts and washers (field supply) as follows:
INFORMATION
The maximum height of the upper protruding part of the
bolts is 15 mm.
(mm)
ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA
Daikin Altherma - Low Temperature Split
4P313775-1C – 2012.11
In order to guarantee good operation of the unit in areas with risk of
snowfall, a minimum of 10 cm needs to be assured below the bottom
plate of the unit. It is recommended to construct a pedestal with the
same height as the maximum snowfall height. On this pedestal it is
then recommended to install the EKFT008CA option kit to guarantee
the minimum space of 10 cm below the bottom plate of the unit.
b
(mm)
a Maximum snowfall height
b EKFT008CA option kit
If the unit is installed on brackets to the wall, it is advised to use the
EKFT008CA option kit and to install the unit as follows:
b
(mm)
a Maximum snowfall height
b EKFT008CA option kit
7 Installation
Installer reference guide
27