Daikin ERLQ004~008CAV3 Reference Manual page 57

Altherma - low temperature split
Table of Contents

Advertisement

#
Code
N/A
[6-00]
The temperature difference determining
the heat pump ON temperature.
Range: 2~20°C (default: 2)
N/A
[6-01]
The temperature difference determining
the heat pump OFF temperature.
Range: 0~10°C (default: 2)
T
DHW
[7-00]
T
73
BH OFF
T
71
BH ON
T
70
U
60
T
50
HP MAX
[6-01]
T
48
HP OFF
[6-00]
T
41
HP ON
40
30
20
HP
10
5
BH Booster heater
HP Heat pump. If heating up time by the heat pump
takes too long, auxiliary heating by the booster
heater can take place
T
Booster heater OFF temperature (T
BH OFF
T
Booster heater ON temperature (T
BH ON
T
Maximum heat pump temperature at sensor in
HP MAX
domestic hot water tank
T
Heat pump OFF temperature (T
HP OFF
T
Heat pump ON temperature (T
HP ON
T
Domestic hot water temperature
DHW
T
User set point temperature (as set on the user
U
interface)
t Time
Timers
#
Code
N/A
[8-00]
Minimum running time for domestic hot
water operation. During this time, space
heating/cooling is NOT allowed, even
when the target domestic hot water
temperature has been reached.
Range: 0~20 minutes (default: 5)
N/A
[8-01]
Maximum running time for domestic hot
water operation. Domestic hot water
heating stops even when the target
domestic hot water temperature is NOT
reached. The actual maximum running
time also depends on setting [8-04].
▪ When
thermostat control: This preset value is
only taken into account if there is a
request for space heating or cooling. If
there is NO request for space heating/
cooling, the tank is heated until heat
pump OFF temperature.
▪ When
thermostat control: This preset value is
always taken into account.
Range: 5~95 minutes (default: 30)
ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA
Daikin Altherma - Low Temperature Split
4P313775-1C – 2012.11
Description
[7-01]
T
= 70°C
U
[7-00] =
3°C
BH
HP
[6-01] =
2°C
[6-00] =
7°C
t
+[7-00])
U
−[7-01])
BH OFF
−[6-01])
HP MAX
−[6-00])
HP OFF
Description
system
layout
=
Room
system
layout
Room
#
Code
N/A
[8-02]
Anti-recycling time.
Minimum time between two cycles for
domestic hot water. The actual anti-
recycling time also depends on setting
[8-04].
Range: 0~10 hours (default: 3) (step: 1/2
hour) (only for EHBH/X).
Range: 0~10 hours (default: 0.5) (step:
1/2 hour) (only for EHVH/X).
N/A
[8-03]
Booster heater delay timer.
Only for EKHW*
Start-up delay time for the booster heater
when domestic hot water mode is active.
▪ When domestic hot water mode is
NOT
20 minutes.
▪ The delay time starts from booster
heater ON temperature.
▪ By adapting the booster heater delay
time versus the maximum running
time, you can find an optimal balance
between the energy efficiency and the
heat up time.
▪ If the booster heater delay time is set
too high, it might take a long time
before the domestic hot water reaches
its set temperature.
▪ The setting [8-03] is only meaningful if
setting [4-03]=1. Setting [4-03]=0/2/3
limits the booster heater automatically
in relation to heat pump operation time
in domestic water heating mode.
▪ Make sure that [8-03] is always in
relation with the maximum running
time [8-01].
Range: 20~95 minutes (default: 50).
N/A
[8-04]
Additional running time for the maximum
running time depending on the outdoor
temperature [4-02] or [F-01].
Range: 0~95 minutes (default: 95).
[8-02]: Anti-recycling time
1
0
1
0
[8-00]
[8-01]
[8-02]
1 Heat pump domestic water heating mode (1=active,
0=not active)
2 Hot water request for heat pump (1=request, 0=no
request)
t Time
[8-03]: Booster heater delay timer
8 Configuration
Description
active,
the
delay
time
is
t
Installer reference guide
57