To Access The Most Used Commands; Basic Configuration; Quick Wizard: Language / Time And Date; Quick Wizard: Standard - Daikin Altherma EHVH08S18CB Installation Manual

Low temperature split
Hide thumbs Also See for Altherma EHVH08S18CB:
Table of Contents

Advertisement

Method
Accessing settings via the breadcrumb in the
menu structure.
Accessing settings via the code in the
overview settings.
See also:
"To access the installer settings" on page 13
"5.3 Menu structure: Overview installer settings" on page 17
5.1.1

To access the most used commands

To access the installer settings
1 Set the user permission level to Installer.
2 Go to [A]:
> Installer settings.
To access the overview settings
1 Set the user permission level to Installer.
2 Go to [A.8]:
> Installer settings > Overview settings.
To set the user permission level to Installer
1 Set the user permission level to Adv. end user.
2 Go to [6.4]:
> Information > User permission level.
3 Press
for more than 4 seconds.
Result:
is displayed on the home pages.
4 If you do NOT press any button for more than 1 hour or press
again for more than 4 seconds, the installer permission level
switches back to End user.
To set the user permission level to Advanced end user
1 Go to the main menu or any of its submenus:
2 Press
for more than 4 seconds.
Result: The user permission level switches to Adv. end user.
Additional information is displayed and "+" is added to the menu title.
The user permission level will stay in Adv. end user until set
otherwise.
To set the user permission level to End user
1 Press
for more than 4 seconds.
Result: The user permission level switches to End user. The user
interface will return to the default home screen.
To modify an overview setting
Example: Modify [1‑01] from 15 to 20.
1 Go to [A.8]:
> Installer settings > Overview settings.
2 Go to the corresponding screen of the first part of the setting by
using the
and
button.
INFORMATION
An additional 0-digit is added to the first part of the setting
when you access the codes in the overview settings.
Example: [1‑01]: "1" will result in "01".
Overview settings
01
00
00
01
15
02
00
04
05
06
08
09
0a
0c
0d
0e
Confirm
Adjust
Scroll
3 Go to the corresponding second part of the setting by using the
and
button.
EHVH/X04~16S18CB + EHVH/X08~16S26CB
Daikin Altherma – Low temperature split
4P384971-1E – 2018.02
Column in tables
#
Code
.
03
00
07
0b
0f
Overview settings
01
00
00
01
15
02
00
04
05
06
08
09
0a
0c
0d
0e
Confirm
Adjust
Scroll
Result: The value to be modified is now highlighted.
4 Modify the value by using the
Overview settings
01
00
00
01
20
02
00
04
05
06
08
09
0a
0c
0d
0e
Confirm
Adjust
Scroll
5 Repeat previous steps if you have to modify other settings.
6 Push
to confirm the modification of the parameter.
7 At installer settings menu, press
Installer settings
The system will restart.
OK
Cancel
Confirm
Adjust
Result: The system will restart.
5.2

Basic configuration

5.2.1

Quick wizard: Language / time and date

#
Code
[A.1]
N/A
Language
[1]
N/A
Time and date
5.2.2

Quick wizard: Standard

Backup heater configuration (only for *9W model)
#
Code
[A.2.1.5]
[5-0D]
BUH type:
▪ 1 (1P,(1/1+2)): 6 kW 1~ 230 V (*9W)
▪ 3 (3P,(1/1+2)): 6 kW 3~ 230 V (*9W)
▪ 4 (3PN,(1/2)): 6 kW 3N~ 400 V (*9W)
▪ 5 (3PN,(1/1+2)): 9  kW 3N~  400  V
(*9W)
Backup heater relay setting
Relay setting
If backup heater
step 1 is active:
1/1+2
Relay 1 ON
1/2
Relay 1 ON
5 Configuration
03
00
07
0b
0f
and
button.
03
00
07
0b
0f
to confirm the settings.
Description
Description
Backup heater operation
If backup heater
step 2 is active:
Relays 1+2 ON
Relay 2 ON
Installation manual