Setting Up The Power Consumption Control; Permanent Power Limitation - Daikin ERLQ004~008CAV3 Reference Manual

Altherma - low temperature split
Table of Contents

Advertisement

5.6

Setting up the power consumption control

▪ The power consumption control:
▪ Is only applicable for EHBH/X04+08 and EHVH/X04+08.
▪ Allows you to limit the power consumption of the entire system
(sum of outdoor unit, indoor unit, backup heater and optional
booster heater).
▪ Configuration: Set the power limitation level and how it has to
be achieved via the user interface.
▪ The power limitation level can be expressed as:
▪ Maximum running current (in A)
▪ Maximum power input (in kW)
▪ The power limitation level can be activated:
▪ Permanently
▪ By digital inputs
INFORMATION
Power
consumption
applications with booster heater.
5.6.1

Permanent power limitation

Permanent power limitation is useful to assure a maximum power or
current input of the system. In some countries, legislation limits the
maximum power consumption for space heating and DHW
production. Example: The maximum power input depends on the
area of the house and an annual fee has to be paid to the electrical
company according to the size of the installed field fuse. By
permanently limiting the maximum power or current of the system,
you can install smaller field fuses.
NOTICE
When the current control is intended to reduce the installed
field fuse sizes, the field fuse will trip to protect the field
wires in case of overcurrents caused by the unit. Make
sure the selection of the field fuse complies with applicable
legislation.
P
i
a
DI
b
t
P
Power input
i
t Time
DI Digital input (power limitation level)
a Power limitation active
b Actual power input
Setup and configuration
▪ No additional equipment needed.
▪ Set the power consumption control settings in [A.6.3.1] via the
user
interface
(for
the
"8 Configuration" on page 41):
▪ Select full time limitation mode
▪ Select the type of limitation (power in kW or current in A)
▪ Set the desired power limitation level
ERLQ004~008CAV3 + EHVH/X04+08S18CA + EHVH/X08S26CA
Daikin Altherma - Low Temperature Split
4P313775-1C – 2012.11
control
CANNOT
be
used
description
of
all
settings,
NOTICE
Mind the following guidelines when selecting the desired
power limitation level:
▪ Set a minimum power consumption of ±3.6 kW to
guarantee defrost operation. Otherwise, if defrosting is
interrupted several times, the heat exchanger will
freeze up.
▪ Set a minimum power consumption of ±3 kW to
guarantee space heating and DHW production by
allowing at least one electrical heater (backup heater
step 1 or booster heater).
5.6.2
Power limitation activated by digital
inputs
Power limitation is also useful in combination with an energy
management system.
The power or current of the entire Daikin system is limited
in
dynamically by digital inputs (maximum four steps). Each power
limitation level is set via the user interface by limiting one of the
following:
▪ Current (in A)
▪ Power input (in kW)
The energy management system (field supply) decides the activation
of a certain power limitation level. Example: To limit the maximum
power of the entire house (lighting, domestic appliances, space
heating...).
D
a
5
4
3
A8P
2
1
b
A
B
C
A Outdoor unit
B Indoor unit
C DHW tank
D Energy management system
a Power limitation activation (4 digital inputs)
b Backup heater
c Booster heater
P
i
a
DI4
DI3
DI1
P
Power input
i
t Time
DI Digital inputs (power limitation levels)
see
a Power limitation active
b Actual power input
Setup
▪ Demand PCB (option EKRP1AHTA) needed.
▪ Maximum
four
digital
corresponding power limitation level:
▪ DI1 = weakest limitation (highest energy consumption)
▪ DI4 = strongest limitation (lowest energy consumption)
▪ For the specification and the connection of the digital inputs, see
"15.6 Wiring diagram – components: Indoor unit" on page 85.