Site Requirements - Baxi Solo 3 30 PF Installation And Servicing Instructions

Wall mounted powered flue gas fired central heating unit
Table of Contents

Advertisement

K
J
G
D
L
Likely flue positions requiring
a flue terminal guard
Terminal Position with Minimum Distance
A
Directly below an openable window or other
opening, e.g. an air brick.
B
Below gutters.
C Below eaves, soil pipes or drain pipes.
D Below balconies or car port roof
E
From vertical drain pipes and soil pipes.
F
From internal or external corners.
G Above ground, roof or balcony level.
H From a surface facing a terminal.
I
From a terminal facing a terminal.
J
Vertically from a terminal on the same wall.
K
Horizontally from a terminal on the same wall.
L
For an opening in a car port (e.g. door, window)
into a dwelling.
Table. 2
Maximum lengths for side flues using the standard telescopic flue kit
410mm (30, 40, 50)
355mm (60, 70, 80)
B,C
G
D
H,I
A
A
E
F
F
G
Fig. 11
(mm)
300
25
75
200
75
25
300
600
1200
1500
300
1200
410mm (30, 40, 50)
355mm (60, 70, 80)
Fig. 12

4.0 Site Requirements

4.3
Flue Position (Cont)
WARNING - The addition of anything that may
interfere with the normal operation of the
appliance (e.g. FLUE DAMPERS,
ECONOMISERS,etc.) without the express
written permission of Baxi UK Limited could
invalidate the appliance warranty and infringe
the GAS SAFETY (Installation and Use)
REGULATIONS.
If a terminal is less than 2 metres (78
above a balcony, above ground or above a flat
roof to which people have access then a
suitable terminal guard must be provided.
6. Table 2 and Fig. 11 show the positioning of the
flue terminal relative to buildings and other
structures.
7. The dimensions of the flue terminal are shown
on page 5.
4.4
Flue Dimensions
1. Flue extensions are available as optional
extras for installations up to 3 metres
(118
1
/
in).
8
2. Vertical flue kits are available up to 4
metres in length. Vertical twin flue kits are
available up to 15 metres in length.
IMPORTANT: Solo 3 30 PF models must not
be set at minimum input when installed with
vertical flue systems.
3. The standard telscopic flue is suitable for use
with rear flue lengths between 100mm (4in) and
500mm (19
5
/
in).
8
NOTE: Maximum flue length when flued to the
left or right is
410mm (16in) - 30, 40, 50 PF
355mm (14in) - 60, 70, 80 PF
4. Where it is intended to pass the flue through a
combustible wall or timber framed dwelling,
reference should be made to the Institute of Gas
Engineers document UP7 - Guide for Gas
Installations in Timber Framed Dwellings.
5. If the flue is more than 1 metre (39 in) long, it
is required that it is supported.
6. All above dimensions are taken from the
respective faces of the outer case.
/
in)
3
4
11