S-G95KE CU-G95KE / CS-G125KE CU-G125KE
(a) Current Transformer Defective
When the Current Transformer (CT) is an open circuit, total running current is less than 1.88A and the indicated frequency is
53 Hz (CU-G95KE) or 74 Hz (CU-G125KE) or above. If this condition continues for 20 seconds, the abnormality signal is sent
from outdoor to indoor after 3 minutes of operation and [H16] is displayed.
(b) 4 Way Valve Defective
(i) Heating Operation (except Deice)
When the indoor heat exchanger temperature is lower than 5°C after 4 minutes of operation, the operation stops and restarts
after 3 minutes. If this phenomenon occurs for 4 times within 40 minutes, [F11] is displayed.
(ii) Cooling Operation
When the indoor heat exchanger temperature is higher than 45°C after 4 minutes of operation, the operation stops and restarts
after 3 minutes. If this phenomenon occurs for 4 times within 40 minutes, [F11] is displayed.
The abnormality is not judged in the following conditions:
• deice operation
• 2 minutes after deice operation
• hot start
• 2 minutes after hot start
• 3 minutes after heating and cooling/soft dry mode changeover