S-G95KE CU-G95KE / CS-G125KE CU-G125KE
(b) Heating Operation
• When the sleep button is pressed, the remote control setting temperature will decrease 2°C after 1 hour or when the remote
control setting temperature is reached. After another hour, 3°C will be decreased again.
13.
Delay On Timer Control
• When the Delayed On Timer is set by using the remote control, the unit will start operate slightly earlier before the set time, so
that the room will reach nearly the set temperature by the On Timer set time.
• 60 minutes before the set time, the indoor fan operates at Lo
intake air temperature and outdoor air temperature in order to determine the starting time for preparatory operation. (The Power
LED blinks during sampling.)
• The time of the preparatory operation will start before the On Timer set time.
(a) Cooling/Soft Dry
14.
Auto Restart Control
• If there is a power failure, operation will automatically be restarted when the power is resumed from 2 minutes.
58 seconds to 3 minutes 52 seconds randomly. It will start with the previous operation mode and airflow direction.
• Auto Restart Control is not available when Timer or Sleep Mode is set.
• J1 at indoor electronic controller should be open circuit to cancel Auto Restart Control.
• During sleep shift operation, indoor fan speed operates at Lo
-
40
and outdoor fan operates for 20 seconds to sense the indoor
(b) Heating
-
.