Protection Control For Heating Operation
a. Intake Air Temperature Control
• When the intake air temperature is 10°C or above and remote control setting fan speed is less than Me
operates maximum at 71 Hz (CU-G95KE) or 90 Hz (CU-G125KE).
• When the intake air temperature is 30°C and above, the compressor operates maximum at 71 Hz (CU-G95KE) or 90 Hz
(CU-G125KE).
b. Outdoor Air Temperature Control
• The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram
below. This control will begin 50 seconds after the compressor starts.
C. High Pressure Control
• The compressor operating frequency is regulated in accordance to the indoor heat exchanger temperature.
47
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE
-
, the compressor