3.
Soft Dry Operation
A. Room Temperature Control
At the start of operation, cooling operation is running until the intake air temperature is 0.5°C higher than internal setting
temperature, then the operation will shift to Soft Dry with indoor fan speed SLo.
• Compressor OFF temperature = Compressor ON temperature.
• The operation frequency changes every 30 seconds.
• 30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
• The Compressor stops when the intake air temperature reaches 3.5°C below internal setting temperature and continues for 3
minutes.
• When the Compressor stops operation, indoor fan stops for 330 seconds.
• When the Compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
• When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation immediately.
• When the Compressor stops, the outdoor fan motor stops 30 seconds later.
21
CS-G95KE CU-G95KE / CS-G125KE CU-G125KE