8.2.
Protection
1.
Protection Control For All Operations
a. Time Delay Safety Control
• The Compressor is not restarted for 3 minutes after stop of compressor.
b. 30 Second Forced Operation
• Once the compressor is ON, it will not turn OFF for 30 seconds. However, it is turned off by remote control or Automatic
switch.
c. Total Running Current Control
• When the outdoor unit total running current (AC) exceeds I1, the frequency is lowered by 1 rank. If I1 is not exceeded for
30 seconds, the frequency is highered by 1 rank at one time. If the outdoor unit total running current exceeds I2, the
compressor is immediately stopped for 3 minutes.
<Cooling, Soft Dry set value>
Note: Zone A will be used 30 minutes after operation starts.
<Heating set value>
Model No.
CU-G95KE
I1 (A)
I2 (A)
• If the outdoor unit total running current exceeds I2 3 times within 30 minutes, all indoor and outdoor relays will be turned off;
TIMER LED will blink and F98 is displayed.
d. IPM (Power transistor) Prevention Control
1. Overheating Prevention Control
• When the IPM (power transistor) temperature rises to 100 ± 10°C, the compressor stops immediately. The compressor
is restarted when the IPM (power transistor) temperature decreases to 90 ± 10°C after 3 minutes (Time Delay Safety
Control). If this condition occurs 4 times within 40 minutes, all indoor and outdoor relays will be turned off; TIMER LED
will blink and F96 is displayed.
Zone A
Model No.
CU-C95KE CU-G125KE CU-G95KE CU-G125KE
I1 (A)
5.3
I2 (A)
7.3
CU-G125KE
6.1
9.2
7.3
10.8
Zone B
6.7
4.3
5.2
10.8
7.3
10.8
42