3.6.3 EPO Function & Digital Input
The communication Module has an emergency power off function (EPO).
Users can customize EPO function in APP or Delta Solar System (DSS).
COMM. card
Figure 3-20: EPO and digital input function terminal block
Once enabled, the EPO function can be used to turn off the inverter through the
relayless contacts connected to terminals [V1 & K0].
A digital power reduction control function is provided, which can be set to limit the
available active output power of the inverter. The control settings for this function
are made by placing a hardware short circuit (jumper or relay) between the two
terminals of the terminal block shown in Table 3-5.
For Australia and Newzealand, please refer to Table 3-6.
Short terminals
V1 & K0
V1 & K1
V1 & K2
V1 & K3
V1 & K4
V1 & K5
V1 & K6
Tabel 3-6: Definition of DRMs for Australia and New Zealand
Short
V1 & K1
V1 & K2
V1 & K3
V1 & K4
V1 & EPO
Table 3-5: Definition of digital input & EPO function
Inverter's action
Emergency power off (EPO)
0% active power
Maximum 30% rated power
Maximum 60% rated power
Maximum 100% rated power
Reserved
Reserved
Inverter's action
DRM5 (0% active power)
DRM6 (Maximum 50% active power)
DRM7 (Maximum 75% active power and sink reactive power)
DRM8 (Maximum 100% active power and sink reactive power)
DRM0 (Emergency power off)