Culligan 9" Owner's Manual page 43

High efficiency twin automatic water softeners
Table of Contents

Advertisement

Recommended Meter Start-Up Procedure
1.
Close the main water supply valve.
2.
Set the Cul-Flo-Valv® to the bypass position.
3.
Ensure that all faucets at the installation site are closed.
4.
Direct the drain line discharge into a bucket where flow can be observed.
5.
Plug the transformer into a 120 Volt, 60 Hz, single-phase receptacle. The screen displays
FIRST TIME SETUP.
6.
Complete the First Time Setup.
7.
Open the main supply valve.
Initiate an immediate regeneration to move the control into the BACKWASH position.
8.
9.
Refer to the section on manual cycling for information on cycling the control through its
positions.
10. When in the BACKWASH position, slowly rotate the bypass to the soft water position until
water flows.
11. Allow the tank to fill slowly until water flows from the drain line.
12. When flow to drain is established, open the bypass fully. Watch the drain line discharge
for signs of resin. If signs of resin particles appear, reduce the flow. Increase the flow
again when resin no longer appears in the discharge.
13. After the BACKWASH runs clear, step the control to the REFILL position to fill the brine
tank and purge air from the brine line.
14. Complete the installation and cleanup.
15. Sanitize the unit as you leave the installation site. See "Sanitizing Procedure" on page 48.
16. Initiate an immediate regeneration, or set to regenerate at the preset time.
Final Startup
01023052
43