6.3 Input Fuse is burnt

Check Items
The IGBT of Inverter Stage is out of order
UPS Output Short Circuit or Overload
PFC is abnormal
FIG. 6.3
Trouble-shooting
1. Check the related circuit as shown in fig.6-4.
Check Q29-Q32, D15, D16, R159, R163, R169
and R172 are defective. If Q29-Q32 are
abnormal, the U8 & U9 need to be replaced,
too.
2.Check Q5, U4 ¡BBD1, BD2 in PFC circuit
(fig6-3).If Q5 is abnormal, replace both U4 and
Q5.
3. Check D32-D35, Q12-Q14, Q24, Q27, Q28 and
U7, Refer to fig.6-5.
Remove the output load. If the UPS works
Normally, it means the output load connected is
in short circuit or overload.
1.Check the related circuit as shown in fig.5-3.
2.Check if the PFC driving IGBT 30N60(Q5) and
the photo coupler IC PC923( U4) are abnormal.
34