Ablerex 3 MS series User Manual page 17

Mars mr series
Table of Contents

Advertisement

Environmental Temperature is out of
windows(
Over 40 degree C)
BUS Voltage abnormal
The feedback signal to CPU is
abnormal.
4.2.2.Fault Status Analysis
When the Fault LED lights up, you may know which part of the UPS is out of order by
Pushing the Test Switch in front.
Utility
Inverter
0
0
0
0
0
0
0
1
0
1
0
1
p.s. A code composed by Utility, Inverter, Battery Low and Overload LEDs may indicate the possible
fault conditions by pushing the Test Switch button in front.
2. Connect 12Vdc t o the Fan(red line to positive) to check if
the fan is normal.
3. Otherwise, please check the related circuit as
fig 4-2.
Improve the ventilation and reduce the temperature of the
environment.
The PFC conrtrol IC U2 or the Booster control IC U9 may be
abnormal.
1. Check if the connection between the control
Board and the driver board is properly done.
2.Check if pin1 of U5(HA17393) of the driver board is sending
out a square wave of Utility frequency.
Battery Low
Overload
0
1
1
0
1
1
0
0
0
1
1
0
Symptom
Short Circuit
Inverter Over-current
Battery Voltage Abnormal
Inverter Voltage Abnormal
Heat Sink Overheat
DC Bus Fault
17