4.3.

Input Fuse is burnt

Check Items
The IGBT of Inverter Stage is out of order
UPS Output Short Circuit or Overload
PFC is abnormal
FIG. 4.3
Trouble-shooting
1. Check the related circuit as shown in fig.4-4.
Check Q14, Q13, D24, D25, R118 and R120
are defective. If Q14¡BQ13 is abnormal, U7,U8
need to be replaced, too.
2. Check Q12, U6¡BBD1 in PFC circuit (fig4-3).
If Q12 is abnormal, replace both U6 and Q12.
3. Check D30-D33, Q15-Q20 and U9, refer to
fig.4-5.
Remove the output load. If the UPS works
Normally, it means the output load connected is
in short circuit or overload.
1. Check the related circuit as shown in fig.4-3.
2. Check if the PFC driving IGBT 20N60(Q12) and
the photo coupler IC PC923( U6) are abnormal.
18