5.3 Input Fuse is burnt

Check Items
The IGBT of Inverter Stage is out of order
UPS Output Short Circuit or Overload
PFC is abnormal
FIG. 5.3
Trouble-shooting
1.Check the related circuit as shown in fig.5-4.
Check Q6, Q7, D12, D13, R83 and R104
are defective. If Q6&Q7 are abnormal, the U6 &
U7 need to be replaced, too.
2.Check Q1, U3¡B BD1 in PFC circuit (fig5-3).If Q1
is abnormal, replace both U6 and Q1.
3. Check D31-D34, Q10, Q12, Q15, Q17, Q19,
Q21 and U9, Refer to fig.5-5.
Remove the output load. If the UPS works
Normally, it means the output load connected is
in short circuit or overload.
1.Check the related circuit as shown in fig.5-3.
2.Check if the PFC driving IGBT 20N60(Q1) and
the photo coupler IC PC923( U3) are abnormal.