Downloading Setting Data To Cpu Unit; Downloading To Execution Memory Ram/Rom1; Copying From Sd Memory Card To Execution Memory Ram/Rom1 - Panasonic FP7 User Manual

Cpu unit programmable controller
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

2.6 Downloading Setting Data to CPU Unit

2.6.1 Downloading to Execution Memory RAM/ROM1

 Overview
 Parameters set in the logging/trace settings menu are downloaded together with programs
and configuration data as project data.

2.6.2 Copying from SD Memory Card to Execution Memory RAM/ROM1

 Overview
 Logging/trace settings auto-run files are copied to the memory RAM/ROM1 for program
execution via SD memory cards.
PROCEDURE
1. Create an "AUTO" folder in an SD memory card.
2. Select "Tool" > "SD Memory Card" > "Create Logging/Trace Settings Auto-
Run File" in the menu bar.
The "Create auto-run file" dialog box is displayed.
3. Select "Create new settings" and LOG numbers, and press the [Yes] button.
The "Browse Folders" dialog box is displayed.
4. Select a desired folder, and press the [Yes] button.
A logging/trace settings auto-run file "logtrc.fp7" is created.
5. Save the created file in the "AUTO" folder in the SD memory card.
6. Insert the SD memory card into the CPU unit.
7. Set the mode switch of the CPU unit to the "COPY" (right-hand side) until
the SD LED and COPY LED flashes.
The logging/trace settings auto-run file "logtrc.fp7" is copied into the execution
memory RAM/ROM1.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net