Troubleshooting

6.2 Troubleshooting

6.2.1 Errors When Start/Stop Operation was Executed Using FPWIN GR7

This section describes the messages displayed when the start or stop operation is performed
on the "Logging/Trace Monitor" dialog box, and countermeasures.
 List of error messages
Error message
60 From PLC:
Application error
- Parameter error
62 From PLC :
Application error
- Registration error
78 From PLC :
Application error
- No SD error
90 From PLC :
Application error
- Logging error

6.2.2 Errors When Operation was Executed Using LOGST, LOGED or SMPL

Instruction
This section describes the situations and countermeasures when logging operation starts or
stops, or logging trigger operation is performed with instructions in user programs.
 List of errors
Situation or
Error messge
ERROR LED turns on.
An operation error
occurred in the address of
LOGST or LOGED
instruction.
An operation error
occurred in the address of
SMPL instruction.
Logging/Trace operation
is not executed with
SMPL instruction.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
6-4
Situation
Any box of LOG number is not
checked.
An unregistered LOG number was
activated.
No SD memory card is inserted, or
the card cover is open.
An attempt was made to download
logging setting parameters during
logging operation.
An attempt was made to display
data on a time chart during trace
operation.
Situation
A self-diagnostic error such as an
operation error occurs.
The instruction might have been
executed for an unregistered LOG
number.
There is a possibility that no SD
memory card is inserted, or the card
cover is open.
The instruction was executed for
the LOG number the logging trigger
of which is not set to "Instruction".
There is a possibility that the LOG
number does not match.
Countermeasures
Check the box of the LOG number to be
started.
Check if the settings matches the LOG
number to be activated.
Check if an SD memory card is inserted,
and close the card cover.
Depending on the situation, wait for the
completion of logging operation, or
download the setting parameters again
after performing the logging stop operation.
Depending on the situation, wait for the
completion of trace operation, or press the
[Time Chart] button after performing the
trace stop operation.
Countermeasures
Wen an operation error occurs in the
address of LOGST, LOGED, or SMPL
instruction, check the followings.
Check if the settings match the LOG
number for which the instruction is
executed.
Check if an SD memory card is inserted,
and close the card cover.
Check if the settings of logging trigger
match the LOG number for which the
instruction is executed.
Check if the settings match the LOG
number for which the instruction is
executed.