3.3 Operation Check Using System Monitor
3.3.1 Monitoring Method of System Monitor Area (SM)
By using the system monitor function, the number of written records in a current file, the
number of files stored in a folder (number of generations) and the oldest clock data of files
stored in the folder can be monitored.
The system monitor area can be monitored with the tool software FPWIN GR7.
PROCEDURE
1. Select "Online" > "Display System Monitor Area (SM)" in the menu bar.
The system monitor dialog box is displayed.
2. Press the [Refresh] button.
The latest information is read.
3.3.2 List of System Monitor Area (SM)
SM211-SM258: Logging/Trace information
SM No.
211-212
For LOG0
213-214
For LOG1
215-216
For LOG2
217-218
For LOG3
219-220
For LOG4
221-222
For LOG5
223-224
For LOG6
225-226
For LOG7
227-228
For LOG8
229-230
For LOG9
231-222
For LOG10
233-224
For LOG11
235-226
For LOG12
237-228
For LOG13
239-240
For LOG14
241-242
For LOG15
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Name
No. of written
records of current
file
3.3 Operation Check Using System Monitor
Description
Stores the number of written records in
a current file as 32-bit data.
One is added every time a file is written,
and it is reset to zero when a new file is
created.