In the Ignored box, the fault codes ignored by the gateway can be listed. Should
several fault codes be entered, they must be separated by a ',' (comma) character.
In the Delayed box, the fault codes listed transferred by the gateway upon the next
connection can be listed. Should several fault codes be entered, they must be
separated by a ',' (comma) character.
Wavenis alarms
8.4.2
When the gateway receives a Wavenis alarm message, it acknowledges it (to the
sending module).
If the alarm is triggered from a known module, the gateway processes it and then
initiates a connection to the remote server in order to lodge it.
If the alarm comes from an unknown module, a Wavenis_unknown alarm is triggered.
This alarm will be sent only once per module and may be sent immediately (On) or
upon the next connection (Delayed).
If the alarm is triggered from a known module but has followed a radio path that is
different from the one configured, an Incorrect route alarm is triggered.
This alarm will be sent only once per module and may be sent immediately (On) or
upon the next connection (Delayed).
The gateway does not filter Wavenis alarms (in other words, there are no parameters
enabling the alarms for a given module to be selected). They may nevertheless be
activated and/or deactivated during configuration of the module itself.
On-off input alarms
8.4.3
Multiple alarms may be configured for digital inputs.
An alarm for a digital input may be configured as follows: