General Vent Installation Information; Installation Of Side Wall Venting - Kingsman HBZDV3624 Installation Instructions Manual

“zero clearance” direct vent gas fireplace
Hide thumbs Also See for HBZDV3624:
Table of Contents

Advertisement

This gas appliance is approved to be vented either through the side wall or vertically through the roof. Only Kingsman Flex(Z-Flex)Venting Kits and
components specifically approved and LABELED for this stove may be used. This appliance is also approved for use with Simpson-Duravent Direct
Vent system (Model DV-GS Series), Ameri-Vent Direct Vent Pipe System, ICC Excel Direct, Metal Fab Sure-Seal DV and Selkirk Direct Temp.
Simpson Dur a-Vent for Masonr y Chimney Conver sion Kits may be used with this appliance Use your existing masonry chimney and route
the exhaust gases intake air through the side of the masonry chimney. Use Simpson Dura-Vent kit numbers 46DVA-KMC or 46DVA-KCT.
Termination Cap, Kingsman/Dura-Vent adapter, and 4" flex are sold separately.
Simpson Dur a-Vent for Factor y built metal Chimney Conver sion Kits may be used with this appliance. Use your existing through the ceil-
ing, wood stove chimney and route the exhaust gases and intake air through the existing wood burning metal chimney. Use Simpson Dura-Vent
Kit numbers 46DVA-KCA for 6 5/8" to 8 5/8" OD sized chimney, 46DV-KCB for 8 3/4" to 10 1/2" OD sized chimneys and 46DVA-KCC for
10 5/8" to 13" OD sized chimneys. Kits 931, 932, and 933 include a cap adapter and Retro Connector. Termination Cap, Kingsman/Dura-Vent
adapter, and 4" flex are sold separately.
RIGID OR HARD PIPE
When using Simpson Duravent, AmeriVent pipe, ICC Excel Direct, Metal Fab Sure-Seal
DV and or Selkirk Direct Temp a Duravent hardpipe adapter must be used (part # ZDVDFA
for fireplaces and part # ZDVDKA for Stoves, Serenity and ZDV3624B). Follow installa-
tion instructions provided by Simpson Duravent/AmeriVent/Selkirk Direct Temp, ICC Excel
Direct, Metal Fab Sure-Seal DV for installation of pipe and adhere to the clearance to com-
bustibles provided in this manual. Apply a bead of Mill Pac high temp sealant to all joints of
pipes, adapters and termination, when using Kingsman Flex(Z-Flex)Venting venting and
Simpson Duravent venting.
NOTE: Increase framing depth by one inch when using hardpipe.
WARNING: DO NOT mix parts from different systems unless stated in the manual.
Flex Pipe Venting
Kingsman Flex pipe is shipped in unexpanded length. When installing pipe expand the
lengths. Pipe can be expanded to twice their lengths e.g. 4ft. to 8ft. Fully expand pipe and
cut off excess.
Do not use more than 2 couplers to extend short pipes. Single sections are preferred in an
installation attaching at the fireplace and termination.
Place the spring spaces provided approximately every two feet to stabilize 4" flex in the cen-
ter of 7" flex. When forming bends place spring in bend or before and after. (See Fig. 1).
Horizontal runs require support metal straps every 2 feet. In off set installation support
straps should be used to stabilize pipe.
Expand 4" and 7" flex pipe to the point that the 7" protrudes approximately 2 to 3 inches past
outer wall and the 4" flex protrudes approximately 2 to 3 inches past the 7" flex. See Fig. 1.
Attach the 4" pipe to the termination first and secure with sealant and screws then attach the
7" flex to the termination with caulking and screws. Termination may then be moved back to
the outer wall and attached to home screwing into the framing. Silicone around termination to
waterproof. If siding shield is going to be used attach this using same attaching hole as the top
of termination after termination has been caulked for water proofing.
Use Hi Temp Sealant
Apply a bead of mill pac high temp sealant to all joints and use four screws to secure each
pipe at fireplace, termination and any joint if joining any sections of pipe.
1. The minimum distance from the bottom of fireplace to centre of vent is 34 inch
(85 cm) (See Figure 1). Cut a hole through the wall allowing for a 11" x 11" (inside diameter) in com-
bustible walls for wall thimble or an 8" diameter hole in a non-combustible wall (See Figure 2).
2. Note clearance to combustible as stated on pages 7 & 8.
3. Select the approximate vent length, precise measurements are not needed as your flex pipe can be expand-
ed to twice its shipped length for ease of installation.
4. To install wall thimble centre over 11" x 11" (inch) framing from both sides of wall and secure. Route
flex vent pipe through wall thimble (See Figure 1).
5. Before joining pipes, apply a bead of high temperature sealant (Mill Pac) to end of pipe. First attach the
four inch (4") flue pipe to the vent termination with sealant, and secure with the four screws provided. At
this time make sure the spacer springs are attached to the (4") flex pipe as required. Then attach the seven
inch (7") pipe by the same method.
6. Mount vent termination and seal to wall using caulking around the wall thimble to weather proof. After
installing the vent termination, double check to make sure the pipe extends properly through wall thimble
and into vent termination.
7. Before joining pipes to fireplace flue, apply a bead of high temperature sealant (Mill Pac) to end of pipe.
First attach the four inch (4") flue pipe to fireplace with sealant, and secure with the four screws provid-
ed. At this time verify that the spacer springs are attached properly to the (4") flex pipe as required. Then
attach the seven inch (7") pipe by the same method.
8. Support horizontal pipes every two (2) feet (61 cm) with metal strap bands. Re-check fireplace to make
sure it is levelled and properly positioned and secured.
9. Support vertical pipes to maintain a minimum of 1" or greater clearance to combustibles with metal strap-
ping bands.
10. If finishing the outside wall with vinyl or wood siding it is recommended that a Siding Shield be installed,
Part Number ZDVSSLR.
Note: Vent Termination must not be recessed into wall or siding.

General Vent Installation Information

Installation Of Side Wall Venting

FRAMING DIMENSION
Combustible Wall
Cut a 11" hole through exterior wall and frame as shown
below.
Non combustible Wall
Cut or drill 8" or 204mm diameter hole.
SEAL WITH HIGH TEMP. SEALANT
MAX. DISTANCE BETWEEN SPACERS 2 FEET
SPRING SPACERS
OPTIONAL
CLAMPS
NOTE: It is critical to the proper and safe operation of
this fireplace that on all connections the inner liner and
the outer casing are both caulked with liberal amounts of
sealant. Do not use any kind of tape or silicone other than
that recommended in this manual, Mill Pac Sealant
30
FIGURE 1
OPTIONAL
CLAMPS
SEAL WITH HIGH TEMP. SEALANT
Note: Wall Thimbles
cover com-
bustible wall up
to 11" thick.
FIG. 1