This gas appliance is approved to be vented either through the
side wall or vertically through the roof. Only Kingsman venting
kits and components specifically approved and LABELED for
this stove may be used.
Flex Pipe Venting
The 5" and 7" Flex pipe is shipped expanded. The 7" flex pipe can be
compressed. The 5" flex is stainless steel and cannot be compressed.
Therefore, the 5" flex pipe will have to be cut to size to fit properly.
Do not use more than 2 couplers to extend short pipes. Single sections
are preferred in an installation attaching at the fireplace and termination.
Place the spring spaces provided approximately every two feet to stabi-
lize 5" flex in the center of 7" flex. When forming bends place spring in
bend or before and after. (See Fig. 1).
Horizontal runs require support metal straps every 2 feet. In off set
installation support straps should be used to stabilize pipe.
Cut 5" and 7" flex pipe to the point that the 7" protrudes approximately
2 to 3 inches past outer wall and the 5" flex protrudes approximately 2
to 3 inches past the 7" flex. See Fig. 1. Attach the 5" pipe to the termina-
tion and secure with sealant and 4 screws then attach the 7" flex to the
termination with sealant and 4 screws. Termination may then be moved
back to the outer wall and attached to home by screwing into the fram-
ing. Silicone around termination to waterproof. If siding shield is going to
be used attach at this time using same attaching hole at top of termina-
tions after termination has been caulked for water proofing.
f i r e - p a r t s . c o m
Use Hi Temp Sealant
Apply a bead of mill pac high temp sealant to all joints and clamp with
screw type clamps provided at fireplace, termination and any joint if
joining any sections of pipe.
1. The minimum distance from the bottom of fireplace to centre of vent is 51 inch
(130 cm) (See Figure 1). Cut a hole through the wall allowing for a 11" x 11"
(inside diameter) in combustible walls for wall thimble or an 8" diameter hole in a
non-combustible wall (See Figure 2).
2. Note clearance to combustible above 90 degree bend in low profile enclosures 58"
is 3"
3. Select the approximate vent length, precise measurements are not needed as your
flex pipe can be expanded to twice its shipped length for ease of installation.
4. To install wall thimble centre over 11" x 11" (inch) framing from both sides of
wall and secure. Route flex vent pipe through wall thimble (See Figure 1).
5. Before joining pipes, apply a bead of high temperature sealant (Mill Pac) to end of
pipe. First attach the five inch (5") flue pipe to the vent termination with sealant
and secure with 4 screws provided. At this time make sure the spacer springs are
attached to the (5") flex pipe as required. Then attach the seven inch (7") pipe by
the same method.
6. Mount vent termination and seal to wall using caulking around the wall thimble to
weather proof. After installing the vent termination, double check to make sure the
pipe extends properly through wall thimble and into vent termination.
7. Before joining pipes to fireplace flue, apply a bead of high temperature sealant
(Mill Pac) to end of pipe. First attach the five inch (5") flue pipe to fireplace with
sealant, then secure with 4 screws provided. At this time verify that the spacer
springs are attached properly to the (5") flex pipe as required. Then attach the
seven inch (7") pipe by the same method.
8. Support horizontal pipes every two (2) feet (61 cm) with metal strap bands.
Re-check fireplace to make sure it is levelled and properly positioned and secured.
9. Support vertical pipes to maintain a minimum of 1" or greater clearance to
combustibles with metal strapping bands.
10. If finishing the outside wall with vinyl or wood siding it is recommended that a
Siding Shield be installed, Part Number ZDVSSLR.

General Vent Installation Information

Installation Of Side Wall Venting

FRAMING DIMENSION
Combustible Wall
Cut a 11" hole through exterior wall and frame as shown below.
Non combustible Wall
Cut or drill 8" or 204mm diameter hole.
FIGURE 1
SEAL WITH HIGH TEMP. SEALANT
MAX. DISTANCE BETWEEN SPACERS 2 FEET
SPRING SPACERS
OPTIONAL
CLAMPS
NOTE: It is critical to the proper and safe operation of this fireplace that on all
connections the inner liner and the outer casing are both caulked with liberal
amounts of sealant. Do not use any kind of tape or silicone other than that
recommended in this manual. Mill Pac Sealant
TOP OF ENCLOSURE
3.000"
58.00"
44.561"
21.625"
0.500"
Gyprock facing
11.0"
THROUGH COMBUSTIBLE
WALL
19
OPTIONAL
CLAMPS
SEAL WITH HIGH TEMP. SEALANT
NOTE:
2 1/4" RISE PER
FOOT OF
HORIZONTAL
RUN
51.00"
FRAMING DETAIL
8" DIA
11.0"
51.0" TO CENTERS
MINIMUM
THROUGH NON-COMBUSTIBLE
WALL
FIGURE 2