Operation Procedure
Operation level
PV/SP
Initial setting level
Input type
Temperature unit

Control period

(OUT1)
Direct/reverse
operation
Operation level
PV/SP
In this example, let's monitor the input type", temperature unit",
direct/reverse operation" and control period (heat)" parameters.
input type" =  ": K thermocouple
temperature unit" =  ": _C

direct/reverse operation" = 

control period (OUT1)" = 20 (secs)"
(1) Press the
key for at least three seconds to move from the opera
tion level" to the initial setting level".
(2) The input type is displayed. When you are setting the input type for
the first time,  ": K thermocouple is set. (0" is set in the case of a
platinum resistance thermometer.) To select a different sensor, press
the
or
keys.
(3) Select the temperature unit" parameter by pressing the
Default is  ": _C. To select  ": _F, press either of the
keys.
(4) Select the control period (OUT1)" parameter by pressing the
key.
Default is 20".
(5) Select the direct/reverse operation" parameter by pressing the
key. Default is 
operation, press either of the
(6) To return to the operation level" press the
second.
Setting Output Specifications
3.5
": reverse operation
": reverse operation. To select 
or
keys.
key.
or
": direct
key for at least one
3–9