F Communications
2–6
• When carrying out communications on the E5GN j03j, connect the
communications cable across terminal Nos.5 and 6.
5
6
B
A
RS-485
E5GN-j03j
Communications Unit Wiring Diagram
Host computer
Shielded cable
RS-485
-
+
FG
A<B : d1c
A>B : d0c
• The RS 485 connection can be either one to one to one to N. Up to 32
units including the host computer can be connected in one to N systems.
Use shielded, twisted pair cable (AWG 28 or larger), and keep the total
cable length to 500 m.
• Specify both ends of the transmission path including the host computer
as the end node (that is, connect terminators to both ends).
The maximum terminal resistance is 54 Ohms.
E5GN (No.1)
E5GN (No.31)
RS-485
No
No
Abbr.
6
A (–)
5
B (+)
Terminator (120Ω, 1/2 W)
RS-485
Abbr.
6
A
5
B