CHAPTER 5 PARAMETERS
Initial Setting Level
ST self-tuning
• The ST (self tuning) function executes tuning from the start of program execution
to calculate PID constants matched to the control target. When the ST function is in
operation, be sure to turn the power supply of the load connected to the control out
Function
put ON simultaneously with or before starting operation of the E5GN.
Parameter
Setting
F Related parameters
ST stable range" (advanced function setting level)
Input type" PID / ON/OFF" (initial setting level)
See
Control period (OUT1)
Control period (OUT2)
• This parameter sets the output period. Set the control period taking the control char
acteristics and the electrical life expectancy of the relay into consideration.
• In a standard control system, use the control period (OUT1)" parameter. The con
Function
trol period (OUT2)" parameter cannot be used.
• In a heating and cooling control system, the control period can be set independently
for heating and cooling. Use the control period (OUT1)" parameter to set the heat
ing side control period, and use the control period (OUT2)" parameter to set the
cooling side control period.
Setting
F Related parameter
PID / ON/OFF" (initial setting level)
See
5–22
Setting Range
: ST function OFF /
ST
Parameter
Control period (OUT1)
Control period (OUT2)
The control must be set to temperature input
and 2-PID control.
Unit
: ST function ON
None
The control must be set to 2-PID control.
Setting Range
Unit
1 to 99
Second
1 to 99
Second
Default
Default
20
20