6.2 User Calibration
F Calibrating input
F Registering
calibration data
The E5GN is correctly calibrated before it is shipped from the factory, and
normally need not be calibrated by the user.
If, however, it must be calibrated by the user, use the parameters for cali
brating temperature input and analog input.
However, note that OMRON cannot ensure the results of calibration by
the user.
Also, calibration data is overwritten with the latest settings. The default
calibration settings cannot be returned to after user calibration.
When the user calibrates the E5GN, the input type currently selected in
parameters is calibrated. The following 22 input types can be calibrated.
• Thermocouple
• Non contact temperature sensor
• Analog input
• Platinum resistance thermometer
The new calibration data for each item is temporarily registered. It can be
officially registered as calibration data only when all items have been cali
brated to new values. So, be sure to temporarily register all items when
you calibrate the E5GN.
When calibration data is registered, it is registered regardless of whether
or not the E5GN has been calibrated by the user.
Prepare separate measuring devices and equipment for calibration. For
details on how to handle measuring devices and equipment, refer to the
respective instruction manuals.
User Calibration
6.2
: 12 types
: 4 type
: 1 type
: 5 types
6–3