MV upper limit
MV lower limit
• The MV upper limit" and MV lower limit" parameters set the upper and lower lim
its of the manipulated variable. When the manipulated variable calculated by E5GN
exceeds the upper or lower limit value, the upper or lower limit set becomes the out
Function
put level.
• MV upper limit
The setting ranges during standard control and heating and cooling control are dif
ferent.
Setting
The manipulated variable at the control output 2 side during heating and cooling
control is expressed as a negative value.
Control Method
Standard (heating)
• MV lower limit
The setting ranges during standard control and heating and cooling control are dif
ferent.
The manipulated variable at the control output 2 side during heating and cooling
control is expressed as a negative value.
Control Method
Standard (heating)
F Related parameters
PID / ON/OFF" (initial setting level)
ST" (initial setting level)
See
Advanced Function Setting Level
The control must be 2-PID control, and the
"ST" parameter must be set to "OFF".
Setting Range
MV lower limit +0.1 to 105.0
Setting Range
-5.0 to MV upper limit -0.1
Unit
Default
%
105.0
Unit
Default
%
-5.0