Communication and configuration
7.5

HART variables

Pos: 19.13.7 /Konfiguration, Parametrierung/Temperatur/TTR200/HART-Variablen Zuordnung @ 15\mod_1195814549281_3101.doc @ 142491
The TTR200 rail unit provides users with 3 HART variables.
The primary variable is mapped to the 4 ... 20 mA output as well as the secondary and tertiary
variables.
The HART variables are assigned the following values:
-
primary HART variable:
(The primary HART variable is mapped permanently to the analog output and is mapped
accordingly to the 4 ... 20 mA signal.
-
secondary HART variable:
-
tertiary HART variable:
Pos: 19.13.8 /Überschriften/1.1/1-spaltig/J - L/Kommunikation / HART-Tag / Geräte-Adressierung @ 8\mod_1174410351609_3101.doc @ 73867
7.6

Communication / HART tag / Device address

Pos: 19.13.9 /Konfiguration, Parametrierung/Temperatur/TTR200/Kommunikation / HART-Tag / Geräte-Adressierung @ 15\mod_1195815541078_3101.doc @ 142514
For ease of identification, each HART device features a configurable 8-digit HART tag.
Standard devices are come with the HART tag "TI XXX".
(When storing HART tags with more than 8 digits in the device, use the "Report" parameter,
which supports up to 32 characters.)
In addition to the HART tag, each device has a HART address.
This address is set by default to zero, in which state the device operates in HART standard
communication mode (point-to-point operation). When an address in the range 1 to 15 is used,
the device switches to HART multidrop mode. This operating mode enables users to connect up
to 15 devices in parallel to a power supply.
In multidrop mode, an analog output signal that matches the process temperature is not
available. The output signal in multidrop mode is a constant 3.6 mA and is used exclusively for
the power supply.
In multidrop mode, sensor or process data information is available only as a HART signal.