Communication and configuration
Device
Description
parameters
When using the transmitter reference
Reference point
point: internally relevant for all
thermocouples except type B, if
thermo/ equalizing conductor is
clamped to the transmitter without
using the transmitter reference point:
without type B, externally fixed
transfer of thermo/ equalizing
conductor via copper material at
constant thermostat temperature
Relevant for external reference point,
Reference point
information on constant external
ext.
reference point temperature
Select the unit of measure for the
Unit
sensor
Defines the sensor measurement
Measurement
start
start
Defines the sensor measurement
Measurement
end
end
Configurable condensation 63 %
Damping
output signal damping value
Configuration data is reset to factory
Factory reset
settings for Pt100 3-wire, 0 ... 100 °C
damping off, override, adjustment
data (trim high/low and DAC
adjustment values are reset to
factory settings)
Configuration data is reset to factory
Device reset
setting for Pt100 3-wire, 0 ... 100 °C
damping off, override
Generates a 3.6 mA high alarm
Override
signal for sensor or device errors,
configurable from 20 ... 23.6 mA
standard 22 mA
Generates for sensor or device error
Underdrive
a low alarm signal, configurable from
3.5 ... 4 mA
HART tag
Defines HART tag name
Defines communication type
Address
(Multidrop)
28
DTM parameters
<Device> <Configuration>
<Sensor / Reference Point>
<Device> <Configuration>
<Sensor / Reference Point Temp.>
<Device> <Parametrize>
<Measuring Range of PV / Unit>
<Device> <Parametrize> <Measuring
Range of PV / Lower Range Value>
<Device> <Parametrize> <Measuring
Range of PV / Upper Range Value>
<Device > <Parametrize>
<Voltage Output / Damping>
<Device>
<Maintenance>
<Reset to Factory Setting>
<Device> <Maintenance>
<Device Reset>
<Device> <Parametrize>
<Current Output / Output with Fault>
<Device> <Parametrize>
<Current Output / Output with Fault>
<Device> <Maintenance>
<Poll Address / Tag>
<Device> <Maintenance>
<Poll Address / Tag>
TTR200
Effective range
internal
None
externally - fixed
-50 ... 100°C
°C, °F, °R, K, mV, Ω
Depending on sensor type
Depending on sensor type
0 ... 100 s
Yes / OK
Override
Underdrive
8 characters, alphanumeric
Address = 0 conforms to HART operating
mode: Point-to-point communication,
4 ... 20 mA output signal address = 1 ... 15
conforms to HART multidrop operating
mode output signal 3.6 mA only the digital
HART readings are available
OI/TTR200-EN