Mantel Requirements

Combustible Mantels
The illustration below details mantel clearances and maximum mantel depth.
Any material that protrudes more than 3/4" from the non-combustible facing is considered a mantel
and must meet the mantel requirements.
Combustible Mantel
12" (305mm)
Maximum
38-1/2"
978mm
Non-Combustible Mantels
Non-combustible mantels must meet the clearances listed for combustible mantels. However, if you do
wish to reduce the clearances by using a non-combustible mantel, the following requirements must be met:
Non-combustible mantel
and facing must extend
from the top of the
appliance to the top
surface of the mantel.
A non-combustible
header must be used
(metal stud).
© Travis Industries
Installation
(for qualified installers only)
Non-Combustible Framing (metal studs)
must be used for the header.
Combustible mantel columns (legs) that protrude more than 3/4"
(0.75mm) from the glass frame must meet the 1" (25mm) sidewall
clearance. If they protrude 3/4" (0.75mm) or less, they may be placed
directly to the side (but not in front) of the fireplace.
Non-combustible mantel columns do not have a minimum clearance.
SIDE OF FIREPLACE
4081126
Drywall
Non-Combustible Mantel
Non-Combustible Facing
100-01210_000
41