Min 34"-Max 52"
Min 28"-Max 36"
DUCTING
A minimum of 6" round or 3-1 /4 x 10"
rectangular duct work must be used to maintain
maximum air ow e ciency with the 600 cfm
internal blower. A minimum of 10" to 8" round must
be used with the 1000 cfm external blower.
Always use rigid type metal duct work only.
Flexible ducts could restrict air ow by up
to 50%.
Use calculation worksheet to compute total
duct work.
ALWAYS, when possible, reduce the number
or transitions and turns. If a reducer is used,
install a long reducer instead of a pancake
reducer. Reduce duct size as far away from
opening as possible.
If turns or transitions are required:
Install as far away from opening and as far
apart, between 2, as possible.
Minimum mount height between range top to hood bot-
tom should be no less than 28".
Maximum mount height should be no higher than 36".
It is important to install the hood at the proper mounting
height. Hoods mounted too low could result in heat
damage and re hazard; while hoods mounted too high
will be hard to reach and will loose its performance and
e ciency.
9"
If available, also refer to range manufacturer's height
clearance requirements and recommended hood
mounting height above range. Always check your local
Min 98"-Max 124"
codes for any differences.
36"
Minimum Duct Size:
Round - 6" minimum at 600 cfm
Round - 10" to 8" minimum at 1000 cfm
Rect angular - 3 1/4" x 10" minimum only if
using internal blower at 600 cfm. Using
rectangular ductwork will require a transition
adapter (not provided, but readily available at
most hardware stores).
DAMAGE-SHIPMENT / INSTALLATION:
• Please fully inspect unit for damage
• If the unit is damaged in shipment , return
• If the unit is damaged by the customer,
• If the unit is damaged by the ins taller (if
5
*Minimum ceiling height of 98". Hood
mounted at 28" above cooking surface.
**Maximum ceiling height of 124". Hood
mounted at 36" above cooking surface.
befor e installation.
the unit to the store in which it was bought
for repair or replacement.
repair or replacement is the responsibility
of the customer.
other than the customer), repair of replace
ment must be made by arrangement
between customer and installer.
Need help?
Do you have a question about the Trapeze CTP-E 48SX and is the answer not in the manual?