3.4 Programming and Passwords

There are two factory set programming passwords which will access the Programming screens as
indicated in the following examples. From either of the screens, access to specific system and
device features or programming may be obtained. All user programming entries are stored in
nonvolatile memory. The factory set passwords can be changed by the user as described in
"Password Change" on page 103. If an invalid password is entered, the blinking cursor will return
See Page
to the first password character position. To exit Programming or Read Status mode at any time,
press the ESC (Escape) key repeatedly. Note that Programming mode must be exited using the ESC
key in order to store the program data entered during this mode. If the Reset key is pressed or
power is lost before exiting Programming mode, the data just entered will not be saved.
To access user Programming mode, press the Enter or Mode key. The LCD will display the
following:
To enter the user Programming mode, press 2. The display will read as follows:
Entering the Master level password (default 00000) will cause the following screen to appear:
If the Maintenance level password (default 11111) is entered, the following screen will appear:
Note that in the two preceding screens, an arrow appears to inform the programmer that additional
options can be viewed by pressing the keypad down arrow key.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FUTURE USE
4=REMOTE DOWNLOAD
PROGRAMMING
ENTER PASSWORD
*****
PROGRAMMING
1=INPUT ZONES
2=NACS
3=RELAYS
PROGRAMMING
1=INPUT ZONES
2=HISTORY
3=WALKTEST
Programming
57