Waterflow Delay; Ac Loss Delay - Honeywell MS-5UD Series Manual

Hide thumbs Also See for MS-5UD Series:
Table of Contents

Advertisement

TIMER
1=PAS DELAY
120
2=PRE SIGNAL
120
3=WATERFLW DELAY
0
Timer Screen #1
TIMER

1=AC LOSS DELAY 2

Timer Screen #2
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of three digits, such as 009 for nine seconds. Upon entering the third digit, the time
delay will be stored in the control panel memory and the display will return to the Delay Screen
which will indicate the new delay time.
Note that the FACP can have both PAS and Pre-signal timers programmed with values but a
zone can only use either the PAS or Pre-signal feature, but not both.

3.5.4.1.3 Waterflow Delay

A delay can be added prior to declaring a waterflow type of alarm. Be careful to include any
built-in delays of the waterflow device. The factory default setting for Waterflow delay is 000
for no delay. To select a Waterflow delay of 01 to 90 seconds for all devices programmed for
Waterflow delay, press 3 while viewing Timer Screen #1. The following screen will be
displayed:
WATERFLOW DELAY
RANGE 00-90 SECONDS
A flashing cursor is positioned in the lower left corner of the display. Enter a delay time
consisting of two digits, such as 25 for twenty-five seconds. Upon entering the second digit, the
time delay will be stored in the control panel memory and the display will return to the Delay
Screen which will indicate the new delay time.
3.5.4.1.4 AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the
length of the desired delay. Press 1 while viewing Timer Screen #2 to display the following:
AC LOSS DELAY
RANGE 00-24 HOURS
A flashing cursor will appear in the lower left corner of the display. The factory default setting
is 02 hours. Type the two digit AC loss reporting delay in hours (00 to 24 hour delay). When
the second digit is entered, the display will return to AC Loss Delay Screen #1.
Note: Upon the loss of AC power at the control panel, relays programmed for AC Loss will
transfer immediately, regardless of the AC Loss Delay setting. If no troubles other than AC
Loss exist in the panel, the System Trouble relay will delay activation for the duration of the AC
Loss Delay setting.
Waterflow Delay Screen
AC Loss Delay Screen #1
Programming
75