Programming
SERVICE TERMINAL
1=RING COUNT
Service Terminal Screen #2
DACT
1=SERVICE TERMINAL
2=SUPERV PHONE LINE
Onboard DACT Screen #2
PROGRAMMING
1=SYSTEM SETUP
2=OPTION MODULES

3=HISTORY

Programming Screen #2
100
3.5.5.4.4.1 Ring Count
The ring count designates the number of rings allowed on the phone line prior to answering an
incoming call from a service terminal. The factory default is 0 which means the control panel
will not answer an incoming call. This entry may be programmed for 1 to 25 rings.
To change the Ring Count, press 1 while viewing the Service Terminal Screen #2. The
following screen will be displayed:
RANGE 00-25 RINGS
A flashing cursor will appear in the lower left corner of the display. Enter the two-digit ring
count which can be a value between 00 and 25. After the second digit is entered, the display
will return to the Service Terminal screen.

3.5.5.4.5 Supervised Phone Line

The Supervised Phone Line feature allows the user to disable the supervision of Phone Line 2
by the DACT when using an alternate means of secondary transmission path. The factory
default setting is Phone Line 2 supervised.
Pressing 2 for Superv Phone Line while viewing Onboard DACT Screen 2 will cause the
following screen to be displayed:
SUPERVISE PHONE LINE
1=PHONE LINE 2
Each press of the 1 key while viewing this screen will toggle the option between Supervise
Phone Line 2 Yes and No.
3.5.6 History
The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing 3 while viewing Programming Screen #2 will display the History options
as shown in the following display:
1=VIEW EVENTS
2=ERASE HISTORY
RING COUNT
Ring Count Screen
YES
HISTORY
History Screen