Installation

2.5 Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-
limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram is
illustrated below.
AC Power
Hot (L1)
Ground
Neutral (L2)
earth
ground
Figure 2.11 Typical UL Power-limited Wiring Requirements
32
Power-limited Circuits
(Class 2)
CAC-5X
MS-10UD FACP
Power-limited Circuits (Class 2)
CAC-5X
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Power-limited
Circuits
(Class 2)
4XTMF
Nonpower-
limited
Circuit
Nonpower-
limited
Circuit
Power-limited
Circuit
(Class 2)