Powering Ann-Bus Devices From Auxiliary Power Supply; Ann-Bus Device Addressing - Honeywell MS-5UD Series Manual

Hide thumbs Also See for MS-5UD Series:
Table of Contents

Advertisement

2.8.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply

Figure 2.19 illustrates the powering of ANN-BUS devices from an auxiliary power supply such
as the FCPS-24FS6/8, when the maximum number of ANN-BUS devices exceeds the ANN-
BUS power requirements.
FCPS-24FS6/8

2.8.2 ANN-BUS Device Addressing

Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled "ANN-BUS" on page 80).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
Note: address (ID Number) DIP switches on some devices may have more than 5 switch positions.
Unless otherwise specified in the documentation supplied with each device, switch positions 6 and
above must be set to OFF.
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
TB3
-24 VDC
+24 VDC
Figure 2.19 Powering ANN-BUS Devices from FCPS-24FS6/8
Address
Switch 5
not valid
OFF
OFF
01
OFF
OFF
02
OFF
OFF
03
OFF
OFF
04
OFF
OFF
05
OFF
OFF
06
OFF
OFF
07
OFF
OFF
08
OFF
ON
MS-5UD/MS-10UD
ANN-BUS
ANN-BUS and power wiring are
supervised and power-limited
Switch 4
Switch 3
Switch 2
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
OFF
OFF
Installation
ANN-80
Switch 1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-10ud series

Table of Contents