Honeywell MS-5UD Series Manual page 61

Hide thumbs Also See for MS-5UD Series:
Table of Contents

Advertisement

INPUT ZONE
1=ENABLED
2=TYPE
3=VERIFICATION
Edit Input Zone Screen #2
See Page
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
Pressing the down arrow key will display additional zone types as indicated in the following
table.
Note: Some of the following Zone Types are not available for Canadian applications. Refer to
"Canadian Option" on page 79 for additional details.
Zone Type
Pull-Station
Waterflow
Waterflow Nonsilenceable
Combo
Combo AutoResettable
2-Wire Detector
Normally Open Contact
Fire
Tamper
Supervisory
Supervisory AutoResettable
Medic-Alert
Hazard-Alert
Tornado-Alert
Proc-Mon
Procmon-AR
AC-Loss-Mon
Ack-Switch
Sil-Switch
Drill-Switch
Reset-Switch
PAS-Bypass
Drill-Switch AutoResettable
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
Note: Almost any Input Zone type can activate an ACC-25/50ZS audio zone and output an
assigned message with the exception of ACKNOWLEDGE, SILENCE, RESET and PAS
BYPASS Switches. The DRILL Switch (or input programmed as a drill switch) will cause all of
the corresponding ACC-25/50ZS audio zones to go active and will output Message 1.
Verification
Alarm verification is used to confirm that a smoke detector activation is a true alarm condition
and not a false alarm. This feature is selected by pressing 3 while viewing the Edit Zone Screen
#2 so that the display reads Verification On. Each time the 3 key is pressed, the display will
toggle between Verification On and Verification Off. For a detailed description, refer to "Alarm
Verification (None or One Minute)" on page 117.
Note that verification can only be enabled for a zone that is programmed as a smoke detector
type. Zones programmed for any other type will not allow the Verification feature to be
enabled. Do not use the verification feature if a mix of smoke detectors and normally open
contact devices are connected to the same zone.
Action When Activated
Fire Alarm
Fire Alarm Delayed (uses waterflow delay)
Fire Alarm (uses waterflow delay)
Fire/Supervisory (uses waterflow delay)
Fire/Supervisory AR, nonlatching (uses waterflow delay)
Fire Alarm
Fire Alarm
Fire Alarm
Supervisory
Supervisory, latching
Supervisory, nonlatching
Supervisory, latching
Supervisory, latching
Supervisory, latching
Piezo
Piezo, nonlatching
Trouble
Acts like panel Acknowledge Key
Acts like panel Alarm Silence Key
Acts like panel Drill Key
Acts like panel Reset Key
Positive Alarm Sequence Disable
Acts like panel Drill Key, nonlatching
Programming
61