Note:
OFTEC qualified engineer. (U.K. Only)
7-A: Recommended Service Intervals
28 second oil
35 second oil
Before carrying out a service it is recommended that the following
E). Ensure flue is unrestricted & operating properly
At the same time check for oil and combustion leaks. Advance to service
ONLY after ensuring that both electric and oil supply to boiler is
Draw off any accumulated water and sludge from the tank by opening the
drain cock. Turn off the oil supply and remove the filter bowl, then wash the
Remove combustion access door for access to baffles and to
Check insulation sealing and its silver foil lining in combustion access door -
replacing when necessary. When refitting this door be careful not to dam-
age the foil and insulation by over tightening.
Check performance of oil-nozzle and replace as necessary.

Ensure correct specification replacement nozzle is used.
Check all oil filters and replace as necessary.
Remove burner and clean blast tube and ensure that airways are clear.
Ensure electrodes are clean, dry, not broken and are set as per burner speci-
Once again check flexible oil lines and connections for damage or
Carry out combustion analysis and ensure that boiler is performing to speci-
fication outlined in manual. Flue conditions may cause deviation from these

Always k k e e e e p p c c a a r r e e f f u u l l r r e e c c o o r r d d of flue gas analysis results
including any verbal and written advice to customer (householder).
Always check carefully for restricted or blocked flue. If possible record
C C O O l l e e v v e e l l s s and advise customer of need to keep boiler room well
SERVICING
Servicing must be carried out by a
Once annually
Once annually
is checked:
A). Smoke
B). CO
2
C). The flue gas temperature
D). Oil pressure
disconnected.
7-B: The Oil Tank
element clean with kerosene.
7-C: The Boiler
clean heat exchanger.
7-D: The Burner
fications.
Clean fan and photocell.
leaks, replace as necessary.
Combustion Check
figures.
ventilated.