Venting; Approved Venting; Vertical Terminations; Horizontal Terminations - kozy heat DULUTH 55801 Installation And Operation Manual

Direct vent gas fireplace
Table of Contents

Advertisement

APPROVED VENTING

Refer to vent systems manufacturer's installation manual for complete installation instructions.
Installation must conform with venting requirements and restrictions as outlined in this manual.
Simpson Dura-Vent DV-GS 4" x 6-5/8" direct vent system (horizontal and vertical terminations).
Ameri-Vent Direct Chimney System 4" x 6-5/8" (horizontal and vertical terminations).
Selkirk Metalbestos Chimney System 4" x 6-5/8" (horizontal and vertical terminations).
ICC Chimney System: 4" x 6-5/8" (horizontal and vertical terminations).
This fireplace is designed to be used with rigid pipe only.
IMPORTANT: Vent cap location must be in compliance with guidelines on page 15 of this manual.
IMPORTANT: Consult local and national installation codes to assure adequate combustion and ventilation air is available.
CAUTION: This gas appliance must not be connected to or joined with any other chimney flue serving another appliance.

VERTICAL TERMINATIONS

TOP
1 inch (25mm)
MINIMUM VERTICAL RISE: 2ft. (610mm) vertical + termination cap.
MAXIMUM VERTICAL RISE: 32ft. (9.754m) vertical + termination cap.
NOTE: Page 14 has information on restrictor installation in conjunction with venting installation. Page 24 has information on restrictor
recommendations depending on burner flame appearance and instructions on installation after venting is completed.

HORIZONTAL TERMINATIONS

Follow vent pipe manufacturer‟s installation instructions for horizontal terminations. Include required 1-1/2" (38mm) top clearance
(at wall pass-thru and 1" (25mm) sides and bottom clearances for approved rigid vent systems.
TOP
1-1/2 inches (38mm) at wall pass thru
MINIMUM: 2ft. (610mm) vertical + 90˚ elbow + 9" (229mm) horizontal + termination cap.
MAXIMUM: 2ft. (610mm) vertical + 90˚ elbow + 12ft. (3.66m) horizontal + termination cap.
NOTE: Horizontal sections require 1/4" (6mm) rise for every 12" (305mm) of travel.
IMPORTANT: To achieve minimum venting requirements, a minimum of 57" (1.45m) from floor or hearth fireplace is setting on to top of
vent pipe is required.
IMPORTANT: Wall pass-thru required for all horizontal runs. Refer to vent manufacturer to determine which pass-thru will work best for
your particular application and wall thickness.

VENTING

VERTICAL VENT SYSTEM CLEARANCES
BOTTOM
1 inch (25mm)
HORIZONTAL VENT SYSTEM CLEARANCES
BOTTOM
1 inch (25mm)
PAGE 13
SIDES
1 inch (25mm)
SIDES
1 inch (25mm)