Circuit Type
SLC Loop
(power-
limited
EIA-485
(power-
limited)
EIA-232
(power-
limited)
M500M,
M501M
(power-
limited)
M500CH
(power-
limited)
24 VDC
Power
Runs
(power-
limited)
NR45-24
Unimode 400 Installation PN 50710:A 10/22/97
Each type of circuit within the Fire Alarm Control System requires use of a specific
wire type to ensure proper circuit operation. The wire gauge of a particular circuit
depends on the length of that circuit. Use Table B-1 to determine the specific wiring
requirements for each circuit.
Compliance with the Federal Communications Commission (FCC) and Canadian
Department of Communication regulations on electrical energy radiation requires the
following: Use twisted-pair shielded wire for any wiring entering or exiting the
Unimode 400 cabinet that is not enclosed in conduit.
Circuit
Wire Requirements
Function
Connects to
Twisted-shielded pair, 12
intelligent and
to 18 AWG. 40 ohms,
addressable
maximum per length of
modules.
Style 6 and 7 loops.
40 ohms per branch
maximum for Style 4
loops.
Untwisted, unshielded
wire, in conduit or
outside of conduit.
Connects to
Twisted-shielded pair
ADT-LCD-80 or
with a characteristic
to Annunciator
impedance of 120 ohms.
Control System
18 AWG minimum.
(ACS) modules
Connects to
Twisted-shielded pair.
PRN, P40
18 AWG minimum.
Remote Printers,
CRT, or PC.
Initiating Device
12-18 AWG. Maximum
Circuit (IDC)
circuit resistance is
20 ohms.
Notification
12-18 AWG. MPS-24A:
Appliance
At alarm current level,
Circuit (NAC)
no more than a 1.2 V
drop at the end of the
circuit, or sized to
provide the minimum
rated operating voltage
of the appliances used.
To annunciators
12-18 AWG. Size wire
and M500CH
so that no more than
1.2 V drop across wire
run from supply source
to end of any branch.
Remote
12 AWG in conduit.
Secondary
Power Source
7DEOH % 8QLPRGH  :LULQJ 5HTXLUHPHQWV
Distance
Typical Wire Type
(feet)
10,000
12 AWG Belden 9583 WPW 999 Genesis 4410
8,000
14 AWG Belden 9581 WPW 995 Genesis 4408
4,875
16 AWG Belden 9575 WPW 991 Genesis 4406
3,225
18 AWG Belden 9574 WPW 975 Genesis 4402
1,000
18-12 AWG
6,000 (max)
Belden 9860 (16 AWG)
50 (without
Belden 9860 (16 AWG)
modem)
To meet 20
12-18 AWG
ohms
To meet
12-18 AWG
1.2 V drop,
or sized to
provide the
minimum
rated
operating
voltage of the
appliances
used.
To meet 1.2
12-18 AWG
volt drop
20 (max)
12 AWG
B-1