$SSOLFDWLRQV
1RWH 5HIHU WR )LUH/LWH $ODUPV
,QF ,QVWUXFWLRQ 0DQXDO IRU WKH
5HPRWH 6WDWLRQ 5HFHLYHU 0RGHO
56
5-4
Figure 5-3 shows typical wiring for NFPA 72-1993 Remote Station Fire Alarm System
(UL-listed Fire-Lite RS82 Remote Station Receiver). Note the following:
1.
This application is intended for connection to a polarity reversal circuit of a remote
station receiving unit with compatible ratings.
2.
All connections are power-limited and supervised except the reverse polarity loop.
3.
Circuit supervision is the responsibility of the receiver.
4.
Remote Alarm and Remote Trouble wiring can leave the building.
5.
Maximum load for each circuit: 10 mA; Reverse polarity output voltage: 24 VDC
(nominal) or 28 VDC (max).
Figure 5-3 shows typical wiring for NFPA 72-1993 Remote Station Fire Alarm System:
)LJXUH 5HPRWH 6WDWLRQ &RQQHFWLRQ 8VLQJ D ;70 0RGXOH
NFPA 72-1993 Remote Station Fire Alarm System
;70
7UDQVPLWWHU 0RGXOH
DFWLYDWHG SRODULWLHV VKRZQ
Unimode 400 Installation PN 50710A 10/22/97
Need help?
Do you have a question about the Unimode 400 Multi-Net and is the answer not in the manual?
Questions and answers