SiBE341027

2.4.2 Compressor PI Control

Carries out the compressor capacity PI control to maintain Te at constant during cooling operation and Tc at
constant during heating operation to ensure stable unit performance.
[Cooling operation]
Controls compressor capacity to adjust Te to achieve target value (TeS).
Te set value (Make this setting while in Setting mode 2.)
Te setting
L
M (Normal)
(factory setting)
3ºC
6ºC
Te : Low pressure equivalent saturation temperature (°C)
TeS : Target temperature of Te (Varies depending on Te setting, operating frequency, etc.)
* On multi-outdoor-unit systems, this control is made according to values of the first-priority unit, which is detected with
the pressure sensor.
[Heating operation]
Controls compressor capacity to adjust Tc to achieve target value (TcS).
Tc set value (Make this setting while in Setting mode 2.)
Tc setting
L
M (Normal)
(factory setting)
43ºC
46ºC
Tc : High pressure equivalent saturation temperature (°C)
TcS : Target temperature of Tc (Varies depending on Tc setting, operating frequency, etc.)
* On multi-outdoor-unit systems, this control is made according to values of the first-priority unit, which is detected with
the pressure sensor.
Function
H
7ºC
8ºC
9ºC
H
47ºC
Detailed Control Functions
10ºC
11ºC